Submits Final Response to IE Bulletin 80-11, Masonry Wall Design. Masonry Wall Review Program Shows 37 Walls Are Acceptable,Two Walls Are Acceptable Since Equipment Was Removed from Wall & 15 Walls Are Not Acceptable
ML20010H358
Person / Time
Site: North Anna  
Issue date: 09/14/1981
From: Leasburg R
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
465, IEB-80-11, NUDOCS 8109240384
Download: ML20010H358 (2)


Text

9 y

4 VIRGINIA ELucTnIc ann PowEn COMPANY Ricitwoxn, VinotwrA 20261 ll 0" U lfj il0. l 8' R.H.LEANanno September 14, 1981 Vacs Psamansm?

NocLsAm Oramanuns Mr. James P. O'Reilly, Director Serial No. 465 Office of Inspection & Enforcement PSE&C/ LUM:lmf U. S. Nuclear Regulatory Comnission Docket Nos. 50-338 Region II 50-339 101 Marietta Street, Suite TWO Atlanta, Georgia 30303 License Nos. NPF-4 NPF-7 $ Y '

fk/ _ o 2

/ '

fr f7 y%r

'];

gr3 ~

Dear Mr. O'Reilly:

6 O' I. E. Bulletin No. 80-11, Masonry Wall Design

% g/

North Anna Power Station - Units 1 & 2 G

R\\4

't,,/ ?..

Enclosed is our final report on I. E. Bulletin No. 80-11 activities' at North Anna Power Station. 'Ihis report provides the results of the masonry wall reevaluation prograa and provides documentation updating our previous subuittals. Rather than 'ccing conprehensive and resubnitting information previously provided, this report contains a summary of the masonry wall review program and references our previcus cubnittals where more detailed information has been provided.

In sumnary, t.he analysis results of the masonry wall reevaluation program for North Anna show that 37 walls were acceptable, two walls were acceptable after equipment was removed from the wall,16 walls were modified, and 15 walls were not acceptable. All of the walls found not to meet the reevaluation criteria required by IE Bulletin 80-11 are located in the Ebel Building. Failure of these walls under extreme seismic,r tornado loading would not jeopardize any safety-related equipment as covered by the Station Technical Specifimtions limiting conditions for operation. 'Ihe analysis results f >r the 15 Fuel Building walls were subnitted to the NBC in Licensee Event Report No. LER 81-062/03L-0 by our letter of August 20, 1981, Serial No. N-81-142. Our future correspondence on this subject win be in response to the LER rather than I.E. Bulletin 80-11.

~ZG ll s

?

do 8109240384 810914 DR ADOCK 05000338 PDR

a f

Visolu A Etzers C AND lbwER COMPANY TC ^

Should you have any questions or require additional information, please contact us.

Very truly yours.,

/

/

R. H. Icasburg.

Enclosure cc: Mr. Victor 3tallo, Director Office of Inspection & Enforcement Mr. Harold 3. Denton, Director Office of Nuclear Reactor Regulatior c.

-2

~~-

. - _ _ _ _, _.., -