Submits Followup Rept to 810728 Transmittal Re Ability of Fire Suppression Sys to Meet Operability Requirements During Sys Mods.During Hydrostatic Test of Relocated Fire Hydrant, Pipe Broke.Alternate Fire Protection Maintained
ML20010F616
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 08/21/1981
From: Yundt C
PORTLAND GENERAL ELECTRIC CO.
To: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
CPY-627-81, NUDOCS 8109100437
Download: ML20010F616 (1)


Text

3 f

5.

s Nac

[*{

h, Portland General Electric Company Trojan Nuclear Plant P.O. Bos 439 gy,j.. ;

Rainier, Oregon 97048 (503)556-3713 August 21, 1981 CPY-627-81 Mr. R. H. Engelken, Director U.S. Nuclear Regulatory Commission, Region V 1990 North California Blvd.

Walnut Creek, CA 94596

Dear Mr. Engelken:

This is a follow-up report on my earlier letter, CPY-533-81, dated July 28, 1981.

During the hydrostatic test of the relocated fire hydrant, a pipe joint separated. Additional work is required before the system is returned to an operational status. We are maintaining the alter-nate fire protection action identified in my July 28 letter.

Fire hydrant No. 4 and its associated piping will be returned to service by August 28, 1981.

Sincerely, C. P. Yundt General Manager CPY/CA0/RQR:na Att,chment 6

c:

D. J. Broehl B. D. Withere 1F f*

i O

h g"

R. L. Sullivan ig]. SEP 101981* g W. S. Orser C. F. Marpe seen m es Shift Supervisors g-

  1. ,, g a'""

f,8 CD8"*

LER Distribution S. G. Banton N

N.

Mr. Lynn Frank, DOE

/

.b h,@N/

8109100437 810821 PDR ADOCK 05000344 4 y\\

F pyg

m m

\\

Portland General Electric Company Trojan Nuclear Plant P.O. Bos 439 July 28, 1981 Rainier, Oregon 97048 CPY-53 b81 (503)556-3713 Mr. R. H. Engelken. Director U.S. Nuclear Regulatory Co: mission, region V 1990 North California Blvd.

Walnut Creek, CA 94596

Dear Sir:

Pursuant to Action paragraph 3.7.S.I.c, the following information is provided.

During system modification, Trojan's Fire Suppression System will not meet operability requirecents as defined in paragraph 3.7.8.1.c.

RDC 80-040, DCP 8, requires fire hydrant No. 4 to be relocated in order to maintain a dependable water supply after temporary on-site construction of the Technical Support Center.

Alternate fire protection for the areas covered during modification are as follows:

1.

Warehouse a.

No smoking throughout warehouse.

b.

Establish a roving fire watch every hour.

2.

Transformers a.

Run. a fire hose f rom fire hydrant No. 6 to the transformer area.

3.

Steam generator feed pu=p lube oil reservoirs a.

Run a fire hose from hose station No. S to the lube oil reservoir area.

4.

Emergency diesel generators (Sprinkler Systems A & B) a.

Run a jumper hose f rom the sprinkler drain to fire hose station No. 5.

b.

Establish a continuous fire watch for the emergency diesel generators.

The No. 4 fire hydrant will be placed out of service on August 3, 1981, and be returned to service by August 21, 1981.

Sincerely, JL C. P. Yundt General Manager dh CPY/CA0/ QR:bb c:

D. J. Broehl C. F. Marpe B. D. Withers Shift Supervisors R. L. Sullivan LER Distribution W. S. Orser

)

W >L of 9L SLOOLS

-