/03L-0:on 810728,bus 4A Failed to Transfer Properly (Startup Acb 4AA05 Did Not Close After Auxiliary Acb 4AA02 Tripped).Probably Caused by Transfer Inhibit Relay 162/4A2 W/Loose Crimp on Coil Wire.Relay Replaced
ML20010E783
Person / Time
Site: Turkey Point 
Issue date: 08/27/1981
From: Pace P
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20010E781 List:
References
LER-81-009-03L-01, LER-81-9-3L-1, NUDOCS 8109080253
Download: ML20010E783 (3)


LER-1981-009, /03L-0:on 810728,bus 4A Failed to Transfer Properly (Startup Acb 4AA05 Did Not Close After Auxiliary Acb 4AA02 Tripped).Probably Caused by Transfer Inhibit Relay 162/4A2 W/Loose Crimp on Coil Wire.Relay Replaced
Event date:
Report date:
2511981009R03 - NRC Website

text

-

1

/

i N pC 70A M 364 U. S. NUCLE AA REGULA70dv COMMessioN LICENSEE EVENT REPORT ceNract sLoco I l 1 1

1 I l

<pt. rase paiNy cR TYPE ALL REQUI AED INFORMATioNI i

lo I t l l Fl LI TIP i S l 41@l0101-l0101010IOl-l01OGl4ilililill@l 1 l si..r24@

s e uc.Nses ccoa 64 s

scawa.w sea a

a 6.ca ua r.,. a CON T lolil 77,$,L @

  • 15 l0l 0!0 121 5!1 @IO 17l 2!8 18l 1 @ l018 !217 I 811 l@

s

.o en

cc<ar wussa w **

av cNT : ara re

?s asaca r aara ao sveNT esscaiPricN.4so racsaats CcNstcuaNCss @

l2!:il During power operation, a reactor trip occurred from 100% power with proper) unit lockout action, but the 4A 4160V bus failed to transfer properly 1

io;3, ;

i 3 ia i I (start-up ACB 4AA05 did not close after auxiliary ACB 4AA02 tripped). Thist i 3 i, j i is reportable pursuant to TS 6.9.2.b.2.

Both diesel generators were t

,i g petable and available during this occurrence. A similar occurrence was l

ia DTR LTeported on LER 251-81-004.

10641 I I

59 7

3 g SY$r('A CAU$f CAL 54 COM8 vau g 000E CCCE

$68 CODE COMPONENr 0CCE tt;g;oog sygc;;g W s_j j E l A l@ @j@ IX l@ IX IX l X ! XIX l X!@ [Zj@ [Zj @

n n

u o

a n

II 3'J f N TI A t CCOV9#f401 R $ 8C A r 8IV'TC M da:80 i evtNr vtam a tron' No.

C0ct rv et Nc,

@ s,'Ca* l i 8 il !

L-J l 01019I Ld 10 I3I LL_J L--J LoJ a

ai u

n u

a

s n

u o

n aYrICN uft Ei 808 4 8

3 *.

V N sac aga CN*tANr

.eob al 22 s8 ras N LxJ@LxJ@

lZl@

l Z_J@

I 0 i olo i I

LY_J @

IN j@

l Z l@

l Z l 9 l919 l@

U 34 h

30 3

40 43 42 43 44 af C AUSE CESCRIPrIO*i AND CO AREC.ivt ACTIOe.s i,iai1The most likely cause of this failure to transfer is thought to be the 1

i ntermittent operation of the transfer inhibit relay 162/4A2 which was found i

i.;,i l with a loose crimp on the coil wire.

Consequent testing of the automatic 3 i,,

i,,,,I transfer, after replacing relay 162/4A2, could

- t replicate the failure.

I liI4 11 30 7

4 9 5

5

% POwgm Crwig$rarVS 5

Y DiSCOvtav c45CpiPrfCN IiisIl_Fj @ l11 0 0 l@l NA l

[A_J@lOperationObservation j

1 8'

'.!riviry CCir wouNro, Criviry @ l toCar.CN en uteasa @

Nr

.sts. sea es arcease l NA l ' i s l L.zJ @ G.J@L NA a

...sc,.Ja..,c,A erscanvies@

wvec=

t-s l i i i l '010 $ l@[Z_J@l NA i

,sas:NNd' NJ',ss casca..riCN@

w ver=

lilall0l00l@l NA

]

7 5 7 51

'2 N

W,', ' " 3 f5'?,':2 "" @

l'i31 J @l NA l

10 I:icI d @ %'sem,,.e, @

sac ust oNtv 33u,}"'

' tiii lri;iti !

l NA sa sa n

e a m

e NAVE oF ##E8AAE3 NCNE:

~

0109080253 810827 PDR ADOCK 05000251 S

PDR

REPORTABLE OCCURRENCE 251-81-009 LICENSEE EVENT REPORT PAGE TWO Additional Cause Description and Corrective Action:

The cause of the reactor trip was a failure (spike) of power range channel N-42 while Channel N-41 was tripped for quarterly calibration (2/4 logic trip).

A thorough investigation in order to find the cause of the failure to transfer between the auxiliary and startup transformers revenled the following:

1.

All electrical circuits to the closing coil of the start-up ACB (4AA05) were checked for continuity and electrical capability with a thorough check of the remote circuits to the 3C11G and 3C11T panels including the lockout relay and its contacts. No trouble was found.

2.

T*-asfer inhibit relay 162/4A2 was checked both physically and electrically, no trouble was found. Relay pick-up was found normal and the drop-out was timed at 15 cy.

3.

Due to the availability of two (2) ACBs from Unit No. 3, it was decided to replace both ACBs (4AA02 and 4AA05) with the correspond-ing AC s from Unit 3.

4.

On July 29, 1981, at 5:12 pm, Unit No. 4 tripped from %55% power after a runback from 100% power with successful transfer of both 4160V buses.

(The transfer was initiated by a safety injection (5.I.) sigual).

5.

Due to the availability of the auxillary breakers, a thorough inspection of the 162/4A2 and 162/4B2 (transfer inhibit relays) was made with the following results:

Relay 162/4A2 coil wire to stud 5 (G.E. relay type 12HGA17C) a.

was found to have a loose crimp on the lug (terminal solderless connector) with the wire pulling out of the lug when the coil was being inspected for possible cracks in the black Lexan spool, b.

No visual cracks of the spool were observed, but, visual evidence of heating was found in the outer plastic wrapping and the small

" coil-No."

label at und the copper wire loops.

)

~

REPORTABLE OCCURRENCE 251-81-009 LICENSEE EVENT REPORT.

PAGE THREE t

l 6.

Disposition:

Both relays, 162/4A2 and 162/4B2 were replaced,with available replacement relays from G. E. (Model No. 178A7409 91) with a time delay setting of N10 cy, using implementation procedure from PCM-78-14.

\\

7.

Conclusion: Although no trouble was found after the trip on July 28, i

1981, a proper transfer occurred on July 29, 1981 (after exercising the relay circuits by test and swapping the ACBs). This demonstrated a return to normal operating characteristics due to unknown causes.

The fact that relay 162/4A2 was found with a loose crimp on the coil wire allows us to increase our suspicion that this relay was intermittent in its performance with a very high probability of being the cause of the failure to transfer.

Since relays 162/4A2 and 162/4B2 were both replaced, our logical estimate is that the possibility of a failure to transfer due to a misoperation of these relays has been greatly reduced if not completely removed.