Forwards LER 81-009/03L-0
Date released: 01/24/2020 Download: ML20010E781


LER 81-009/03L-0:on 810728,bus 4A Failed to Transfer Properly (Startup Acb 4AA05 Did Not Close After Auxiliary Acb 4AA02 Tripped).Probably Caused by Transfer Inhibit Relay 162/4A2 W/Loose Crimp on Coil Wire.Relay Replaced
ML20010E783
Person / Time
Site: Turkey Point 
Issue date: 08/27/1981
From: Pace P
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20010E783 (3)
Forwards LER 81-009/03L-0
ML20010E780
Person / Time
Site: Turkey Point 
Issue date: 08/27/1981
From: Schmidt A
FLORIDA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20010E780 (1)