Text
- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
O August 28, 1981
. h5UJk Docket No. 50-29 Q'
LS05-81 08-083 Q SEp 9 Q.
Senior Engineer - Licensing
{A
[/
fir. James A. Kay Yankee Atomic Electric Company
'o 25 Research Drive Westborough, fiassachusetts 01581
Dear !!r. Kay:
SUBJECT:
SEP TOPIC VIII-3.B. DC POWER SYSTEf1 BUS VOLTAGE M0!!ITORIliG AND A!iNUNCIATI0tl, SAFETY EVALUATION FOR YA: KEE R0WE The enclosed staff safety evaluation is based on a contractor's document that has been nade available to you previously. This docunent supports the findings of the staff safety evaluation of Topic VIII-3.B and reconrends rodifications to the dc systems.
The need to actually implerent these changes will be determined during the integrated safety assesscent. This safety evaluation nay be revioed in the future 'f your facility design is changed or if 'iRC criteria relating to this topic are rodified before the integrated assessrent is completed.
Sincerely, Dennis fl. Crutchfield, Chief Operating Reactors Branch No. 5 Division of Licensing
Enclosure:
As stated cc w/ enclosure:
See next page g
gjj-fiff 8109030136 810828 p(d M6I
")
PDR ADOCK 05000029 P
PDR f, ; /,
SEPB:DL SEPB:DL SEPB: QLjt V URB =b:UL:FM U
!_:L f:5A:UL
,[] hoTiTdk
' Rc{u(5' NermaK6' T. Esse'ir DC tc fisTd diss" 8/TfIl1 8/A[8I 8/k/81 8db/81 8/M/81 8/$/.81 g,y Mc Nau m o o vcv cu OFFICIAL RECORD COPY c. w.e.o
Mr. James A. Kay cc Mr. James E. Tribble, President Yankee Atomic Electric Coi.pany 25 Research Drive Westborough, Massachusetts 01581 Greenfield Coimunity College 1 College Drive Greenfield, Massachusetts 01301 l
Chairman f
Board of Selectmen Town of Rowe Rowe, Massachusetts 01367 Energy Facilities Siting Council 14th Floor One Ashburton Place Boston, Massachusetts 02108 U. S. Et vironmental Protection Agency Region I Office ATTN: E.S COORDINATOR JFK Federal Building Boston, fassachusetts 92203 Resident inspector Yankee Rowe Nuclear Power Station c/o U.S. NRC Post Office Box 28 Monroe Bridge, Massachusetts 01350
1Y1IDIAT K IVALUATION PROGRAM TOPIC VIII-3.B YANKEE R0WE TOPIC:
VIII-3.B, DC POWER SYSTEf1 BUS VCLTAGE MUNITORIriG AND ant;Uf;CIATION 1.
INTRODUCTION To assure the design adequacy of the dc power system battery and bus voltage monitoring and annunciation schemes such that the operator can (1) prevent the loss of an emergency dc bus; or (2) take timely correc-tive action in the event of loss of an emergen'cy dc bus, we reviewed the dc power system battery, battery charger, and bus voltage monitoring and annunciation design with respect to dc power system operability status indication to the operator.
II.
REVIEW CRITERIA The review cr.teria are presented in Section 2 of EG&G Report 1349F, "DC Power System Bus Voltage Monitoring and Annunciation."
III.
RELATED SAFETY TOPICS AND INTERFACES fione IV.
REVIEW GUIDELINES None V.
EVALUATION As noted in EG&G Report 1349F the Yankee Rowe control room has no indication
'of dc bus voltage, battery current, battery charger current, or breaker / fuse status.
Therefore, the Yankee Rowe dc power system monitoring is not in compliance with current licensing criteria.
VI.
CONCLUSION The staff proposes that as a minimum, the following additional indications and alarms of the Class lE dc power system (s) status shall be provided in the control room.
l Battery current (ammeter-charge / discharge)
Battery charger output current (ammeter)
DC bus grcund alarm (for ungrounded system) l i
Battery breaker (s) or fuse (s) open alarm Battery charger output breaker (s) or fuse (s) open alarm DC bus voltage