Dm6 50.ssTe)

M H Q 's FsIc coou KANSAS GAS AND HECTMC COMPANY T>E ELE CTr'tC COMPANY GLENN L MOESTER vtCE Pef tsDga t i envCLgan r

August 13, 1981 Mr. G.L. Madsen, Chief i r 2,]4/k Reactor Projects Branch qc U.S. Nuclear Regulatory Commission

's Region IV

/

611 Ryan Plaza Drive

,')

Suite 1000 6

b g

P Arlington, Texas 76011 10pion g r --

k,'

u.5 To"M s5Cd h

KMLNRC 81-105 h

y

g _ __l Re:

NRC Docket No. STN 50-482 g

( U1 '

Subj: Potential 50.55(e) Report GE AKR Circuit Breaker Screws

Dear Mr. Madsen:

On July 14, 1981, Kansas Gas and Electric Company made a telephone report to Mr. W.A. Crossman (NRC) regarding loose and/or bent screws in the closing mechanisms of GE AKR r.ircuit breakers. These screws, when displaced, have the potential for preventing the breaker from closing.

The Architect / Engineer has reviewed and approved the Vendor's inspection and adjustment procedure (GE No. WC-19, Rev. 2 dated 8/6/81) for the GE AKR low voltage power circuit breaker spring and link assemblies.

Startup Field Report (SFR) - NG-2 will be used to document the re-adjustment and/or repairs to the GE AKR 30/50 circuit breaker spring and link assemblies at the Wolf Creek Generating Station Site.

We will submit a report on this inspection and adjustment program on October 16, 1981. Please advise if you need any additional information at this time, gg Yours very truly, f

Q M Z/

Q GLK:bb cc: TVandel, NRC Resident Inspector 81082000 %

2 PDR ADOCK O PT)R S

201 N. Market -Woctuta Kansas -Mad Address: PO. Box 208 I W1chita, Kansst 67201 -Telephone: Area Code (316) 261-6451

-