Forwards Corrected Sheet for Section 5.1.1 of Test Spec to Be Used to Environmentally Qualify Conax Electrical Penetration Canisters at Facility
ML20010B937
Person / Time
Site: Fort Calhoun 
Issue date: 06/30/1981
From: William Jones
OMAHA PUBLIC POWER DISTRICT
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
NUDOCS 8108180498
Download: ML20010B937 (2)


Text

M ? ?-si s

5.,

Omaha Public Power District 1623 HARNEY a OMAHA. NEBRASKA 68102 a TELEPHONE 536-4000 AREA CODE 402 June 30, 1981

/5f) I-)7/.Q,/\\

I b\\

Mr. K. V. Seyfrit, Director U. S. Nuclear Regulatory Commission

y g
  • h.

f Office of Ir.spection and Enforcement ig'-

AUG 171981> 12 Region IV 611 Ryan Plaza Drive, Suite 1000 "W

Arlington, Texas 76011 4

/

4 d

Reference:

Docket No. 50-285

/g Dear P".

Seyfrit:

Omaha Public Power District's letter to the Commission dated June 15, 1981, included a copy of the test specification to be used to environmentally qualify the Conax electrical penetration canisters used at the Fort Calhoun Station.

In section 5.1.1 of that test specifi-be 1.5 x 10 pographical error was found; the leakage rate allowed should caticq, a ty standard CC of helium per second, not 1.5 x 10+6 Accord-0 ingly, the attached corrected sheet should be inserted in the test specification 'n place of the existing sheet.

Sincer,ely,

.: 0 I W. C.jflY'?,7 b

f;C Jones i

Division Manager Production Operations WCJ/KJM/TLP:jmm l

Attachment cc:

U. S. Nuclear Regulatory Conmission Office of Inspection and Enforcement Washington, D.C.

20555 LeBoeuf, Lamb, Leiby & MacRae 1333 New Hampshire Avenue, N.W.

Washington, D.C.

20036 l

hI \\

8108180498 810630 l

PDR ADOCK 05000295 p

PDR

e7 9

5.0 TEST SPECIFICATIONS (Continued) 5.1.1 Leakage Pressura Test - The leakage rste of a penetration cani-ster assembly shall not exceed 1.5 x 10 8 standard CC of helium per second when tested at. 69 psig for a period of 10 minutes.

The leakage to be measured is out of the test canister past the teflon seal.

5.1.2 Continuity Test Each conductor of each feedthrough shall be verified for centinuity.

- ~ ~ - - -

5.1.3 Insulation Resistance Test - The insulator of resistance of each conductor to the other conducto s and sheath shall be measured at 500 -VDC.

The minimum insub: tion resistance shall be 104 megohms.

5.1.4 Voltage Withstand Test - Each feedthrough assembly shall be sub-jected to a voltage withstand test between each conductor and all other conductors and sheath conaected together of 2,200 V 60 HZ for not less than one mi te.

5.1.5 Aging -' The sub-components of the pener.rators shall be aged ac-cording to Table 1 att;ched.

The aging time shall be 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> at 150 C or 1548 hours0.0179 days <br />0.43 hours <br />0.00256 weeks <br />5.89014e-4 months <br /> at 150 C.

5.1.5a Seismic - Seismic testing of the electrical penetrations shall be done in accordance with IEEE-344 1975 and Regulatory Guide 1.100.

Penetration canisters are rigidly mounted in the contain-ment with the sub-assemblies mounted in the canisters as shown in drawing 2325-7684 attached. During a seismic event the motion experienced by the penetrations will be the same as the structure Figures XB 545 S-38 and S-39 showing the structure accelerations.

i For purposes of testing, acceleration at the 1050'-0" elevation shall be used. A 1.5 Lultiplication factor shall be used for the test accelerations.

The test shall conaist of 5 OBE and the followed by 1 DBE events.

Step 5.1.1, 5.1.2, 5.1.3. and 5.1.4 shall be completed following the seismic testing. From Figures 1 and 2 attached, the natural frequencies are 3 hertz horizontal and 9 hertz vertical.

The absolute containment vertical accele-i ration is given in Figure XB545S-38 and S-39 through the entire spectrum.

5.1.6 Radiation - Penetrations are to be irradiated to 2 x 10?R total integrated gamma dose.

Repeat 5.1.1, 5.1.2, and 5.1.4 - each 6

2 x 10 R increment.

5.1.7 Design Basis Accident - The assemblies shall be subjected to the following accident conditions, as outlined in the attached test profile.

305

  • F 74 psig 1900 ppm boron chemical spray buffered with sodium hydroxide for.

a ph of 9.0 at 0.6 GPM per square foot 1

y

,, - ~, -.

n e

~

.