05000331/LER-1981-030-03, /03L-0:on 810701,torus Atmosphere Sampling Line Isolation Valve SV-8108A Would Not Close During Testing. Caused by Rust in Mechanical Portion of Solenoid,Impeding Proper Operation.Solenoid Dismantled & Cleaned

From kanterella
(Redirected from ML20010A602)
Jump to navigation Jump to search
/03L-0:on 810701,torus Atmosphere Sampling Line Isolation Valve SV-8108A Would Not Close During Testing. Caused by Rust in Mechanical Portion of Solenoid,Impeding Proper Operation.Solenoid Dismantled & Cleaned
ML20010A602
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 07/31/1981
From: Schmich A
IES UTILITIES INC., (FORMERLY IOWA ELECTRIC LIGHT
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20010A596 List:
References
LER-81-030-03L, LER-81-30-3L, NUDOCS 8108110597
Download: ML20010A602 (2)


LER-1981-030, /03L-0:on 810701,torus Atmosphere Sampling Line Isolation Valve SV-8108A Would Not Close During Testing. Caused by Rust in Mechanical Portion of Solenoid,Impeding Proper Operation.Solenoid Dismantled & Cleaned
Event date:
Report date:
3311981030R03 - NRC Website

text

>-

cm.us r3 v.s. NUCLEAA AEGULATORY c0MMisS3CN (1.r11

' LICENSEE EVENT REPORT ccNicoLEtecci i

l i

1 l

l (Pt Asa rnini ca rY 4 Au. cacuira3 tNFO; Mart!N1 i

lo ill l IlA !O lA JC l1 l@{ O ! 01 l 0 l 01 O l 0 ! O I 10 l 0 l@l 4 l 1 ! t I 1 I i l@l I

l@

7 4 1 WCE~s44CCCE le 15 uCE%34N'usam 29 24 uC1434 Tvrt JC 57 U T $4 CON'T lolil Z',"c'[_Lj@l015 10 f0 10131311 @l 01710 l i l B l 1 @l0 ! 71311 ! R I 1 l@

i 4

64 61 CCCit ET Nt,uega 6d 69 EVENT DATg 74 75 dEPQRYQATE 40 evsNr otscaiancN ano anceast.s ccNsacussess @

I o 121 l During surveillance testing, torus atmosphere sampling line isolation val I

i ve SV-8108A would not close. Redundant isolation valve SV-8107A was opera l

io i2i lo # 41 I ble and was placed in the closed position complying with Tech. Spec. 3.7.

l Io # si I D.2. flo previous similar occurrences with SV-8108A have been recorded.

I Io !s I l 1

lo t 7l l I

t o is i I F

g g I

40 sysTru CALSE CAust CCup.

vatv g C' 0t CCot SUSCCCE CCMPCNENT CCOE

$UsCCCE SUSCCCE 4

l B l B l@ LE_j@ l D l@ l V I Al L l VI 01 Pl@ l Fl@ L_2,j @

loisi F

8 9

'O II 82 f3

,e t3 20 S ECUE NTT AL CCCURRENCE REPcm7 "EV'58CN Lgmino tytNTytan AEPCRT NC.

CCCE TYPt No.

@,atg; I8i1I l-l l of 3! Of l/l 10 l3 i LU l-l LD_J u

._ v u

n 2

2.

u n

n 2a 2,

n i

TA N aCT CN CN8 NT vtf MOUAS 58 i

PCmW S.

$ 78i.

%i ANU F

.EA LB_j@2.Z_J@

L

.1J@

L.7J@ l 0l 01 01 01 lY !@

l N l@

iAl@

l T I 0 l 2 ! Ol@

L n

u o

y u

o caust cascarencN Ano ccA AECTiVE ACT!CNS h litolisninnnia Valvo sV_91n9A nnncinenrn wne canena ho rnet in'thn enchnnical I

li t i i l nortion of the solenoid which imoeded crocer solenoid coeration. The sol I

iii21 Lenoid was dismantled and cleaned. SV-8108A was then tested and found sat I

l i i a l l isfactory. SV-8108A is a Target Rock model 72V-003 solenoid va lve. A cam l

Iii4 I I ple of similar. valves will be insoected.

I s

a >

STA

  • n* Cwt.

CTl*ER STA T'as is C Rv CisCCV ERY C ESCniPTTCN

~

liIsl LE.j @ 10 l 6 ! 3l@ l NA l-L...B_J@iSurveillance Test l

e a,g,,,,,, g,,,,

u LZj

,oovNT C,.CTiviry @ l toc 47, enc,mus,@

.eu.se@o x..u.se l NA l'isl @'

....sCN~/..@.C S u l NA C.,C.,.7,CN @

r...

U 11] I ol ni n!@lI_J@l NA l

,.sCNN.'L,N,u,

s

=

l Cuca,TicN@

~uo...

li u l 1 n! ni ol@lNA l

u

'4s * "[3

',G'e'N ' ' '" @

v M l] j@l NA l

i.

issu, 7 $e7Cn,, Tie @

NRc uSE CNLY M LL.lb,lMa l

lIII!!!Il!!!I;i s s o

8108110597 8107hj"'ER amOld U Schmich PDR ADOCK 05000331 pMONE:

319-851-5611 I-i 6

p PDR_

.1

N.

p.

j?,

c:

I DUANE ARNOLD ENERGY CENTER Iowa Electric Light and Power Company Licensee Event Report - Supplemental Data Docket No. 050-0331 I;

Licensee Event Report Date:

7-31-81 Reportable Occurrence No: 81-030 i-f

Event Description

During surveillance testing, torus atmosphere sampling line isolation valve SV-8108A would not close.

Redundant isolation valve SV-8107A was~ ope able and was placed in the closed position complying with Tech. Spec. 3.7.D.2.

i No previous similar occurrences with SV-8108A have been recorded.

Cause Description Solenoid Valve SV-8108A nonclosure was caused by rust in the mechanical portion I

of the solenoid which impeded proper solenoid orcration.

Corrective Action

The solenoid was diamantled and cleaned. SV-8108A was then tested and found cat-isfactory.

SV-8108A is a Target Rock model 72V-003 solenoid valve. A representative sample of similar valves will be inspected to determine if this problem is generic in nature. This inspection will be repeated in approximately six months to determine if the. problem is recurring.

r 4

t 1

5 Page 1_ of 1