O n18 so s e m e q u ir a e KANSAS GAS AND ELECTRIC COMPANY 00 THE ELECT 4C COMPANY GLENN L MOESTER WWE Pot s DEN T ewct.tae July 23, 1981 Mr. G.L. Madsen, Chief 4

-I"',[

( ' h ( (tf {['

/s p

Reactor Projects Branc a U.S. Nucle.lc Regulatony Commission wi Region IV 611 Ryan Plaza Drive, Suite 1000 y

<o O 3 E3l

  • C l Arlington, Texas 76011

' \\

u.s. tarn tow:n

~

co m u oi

/, j A

\\ C4' b' V6 KMLNRC 81-101 Re: Docket No. STN 50-482 to Ref: Letter KMLNRC 81-095 dated 6/29/81 from GLKoester, KG&E, to GLMadsen, NRC Sub: Potential 50.55(e) Report - Dravo Piping Spools

Dear Mr. Madsen:

On May 1, 1981, Mr. Wm. G. ~

made a telephone report to Mr. W. Hubacek of your off.

.garding a potential deficiency of some of the Class I and Class III pipe spools supplied by Dravo Corporation. Background information can be found in the letter that Dram sent to the NRC Region III Office (Dravo letter, Schwab to Keppler, dated 1/26/81).

A re-insr action program for Dravo piping spools has been completed at the Wolf Creek Generating Station. The Reference Report indicated that the radiograph review did not identify any weld defects.

How-I l

ever, surface roughness on some welds prevented meaningful liquid l

penetrant examination. Subsequent weld surface preparation has resulted in acceptable examination data.

The final disposition of this weld re-inspection program has indicated that there were no defective welds. Therefore, since there were no significant defects or breakdown of QA proced tres which would adversely affect the safety of the plant, we have concluded that this matter is not reportable under Regulation 10CFR50.55(e).

If you require any additional information, please contact us.

Yours very truly, 3

i.)Y siWC lo GLK:bb cc: TVandel, NRC Site Inspector 8108040282 810723 PDR ADOCK 05000482 S

PDR 201 N Market - Wichita, Kansas - Mail Address: PO. Box 208 I Wichita, Kansas 67201 - Telephone: Area Code (316) 261-G451 J