| 05000331/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | |
| 05000331/LER-1981-002-03, /03L-0:on 810106,temp Switch Tis 4477,zone 2, Tripped Outside Tech Spec.Caused by Instrument Drift.Switch Recalibr | /03L-0:on 810106,temp Switch Tis 4477,zone 2, Tripped Outside Tech Spec.Caused by Instrument Drift.Switch Recalibr | |
| 05000331/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | |
| 05000331/LER-1981-003-03, /03L-0:on 810108,drywell Particulate Radiation Element Re 8101B Found Inoperable.Caused by Sensor Failure Due to Condensation on Particulate Detector.New Radiation Element,Mylar Window & Beta Phosphor Installed | /03L-0:on 810108,drywell Particulate Radiation Element Re 8101B Found Inoperable.Caused by Sensor Failure Due to Condensation on Particulate Detector.New Radiation Element,Mylar Window & Beta Phosphor Installed | |
| 05000331/LER-1981-004-03, /03L-0:on 810111,drywell Particulate Radiation Monitor B Failed Downscale.Caused by Condensate on NMC Model RAK-221F Radiation Element Re 8101B.Design Review Initiated & Particulate & Iodine Filters Examined Daily | /03L-0:on 810111,drywell Particulate Radiation Monitor B Failed Downscale.Caused by Condensate on NMC Model RAK-221F Radiation Element Re 8101B.Design Review Initiated & Particulate & Iodine Filters Examined Daily | |
| 05000331/LER-1981-004, Forwards LER 81-004/03L-0 | Forwards LER 81-004/03L-0 | |
| 05000331/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | |
| 05000331/LER-1981-007-03, /03L-0:on 810219,during Normal Operation,Pressure Differential Across RHR Svc Water Strainer 1S-90B Read High, Resulting in Loop B Inoperability.Caused by Sand Plugged in Strainer Mesh.Strainer Cleaned | /03L-0:on 810219,during Normal Operation,Pressure Differential Across RHR Svc Water Strainer 1S-90B Read High, Resulting in Loop B Inoperability.Caused by Sand Plugged in Strainer Mesh.Strainer Cleaned | |
| 05000331/LER-1981-008-03, /03L-0:on 810212,during Preventive Maint, Recirculation Pump B Tripped Upon Restart,Recirculation Pump Motor Hi/Lo Oil Level Alarm Activated & Would Not Clear.Caused by Lack of Oil in Recirculation Pump Motor B | /03L-0:on 810212,during Preventive Maint, Recirculation Pump B Tripped Upon Restart,Recirculation Pump Motor Hi/Lo Oil Level Alarm Activated & Would Not Clear.Caused by Lack of Oil in Recirculation Pump Motor B | |
| 05000331/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | |
| 05000331/LER-1981-010-03, /03L-0:on 810224,fan for Standby Filter Unit B Found Not Running During Operational Test.Caused by Personnel Error in Opening Breaker for Control Bldg Emergency Air Supply Fan.Personnel Reinstructed | /03L-0:on 810224,fan for Standby Filter Unit B Found Not Running During Operational Test.Caused by Personnel Error in Opening Breaker for Control Bldg Emergency Air Supply Fan.Personnel Reinstructed | |
| 05000331/LER-1981-010, Forwards LER 81-010/03L-0 | Forwards LER 81-010/03L-0 | |
| 05000331/LER-1981-011-03, /03L-0:on 810310,condensate Storage Tank a Low Level Switch LS 5218 Was Found Inoperable.Caused by Moisture on Probe Leads within Terminal Box.Moisture Removed.Switches Will Be Rewired | /03L-0:on 810310,condensate Storage Tank a Low Level Switch LS 5218 Was Found Inoperable.Caused by Moisture on Probe Leads within Terminal Box.Moisture Removed.Switches Will Be Rewired | |
| 05000331/LER-1981-011, Forwards LER 81-011/03L-0 | Forwards LER 81-011/03L-0 | |
| 05000331/LER-1981-012-01, /01T-0:on 810321,pump Discharge Valve MOV 4628 Would Not Close W/Control Room Switch.Probably Caused by Burned Contacts at Motor Control Center.Contacts Replaced | /01T-0:on 810321,pump Discharge Valve MOV 4628 Would Not Close W/Control Room Switch.Probably Caused by Burned Contacts at Motor Control Center.Contacts Replaced | |
| 05000331/LER-1981-012, Forwards LER 81-012/01T-0 | Forwards LER 81-012/01T-0 | |
| 05000331/LER-1981-013-01, /01T-0:on 810324,MSIVs 4412,4413,4416,4418,4419, 4420 & 4421 Found W/Seat Leakage on Inboard & Combined Seat & Steam Leakage on Outboard Valves.Cause Under Investigation.Valves Will Be Repacked & Repaired | /01T-0:on 810324,MSIVs 4412,4413,4416,4418,4419, 4420 & 4421 Found W/Seat Leakage on Inboard & Combined Seat & Steam Leakage on Outboard Valves.Cause Under Investigation.Valves Will Be Repacked & Repaired | |
| 05000331/LER-1981-013, Forwards LER 81-013/01T-0 | Forwards LER 81-013/01T-0 | |
| 05000331/LER-1981-014-01, Four Relief & Safety Valves Found Out of Spec.Cause Unknown.Relief Valve Pilot Assemblies Cleaned,Reworked & Satisfactorily Retested. Safety Valve Will Be Disassembled & Reworked | Four Relief & Safety Valves Found Out of Spec.Cause Unknown.Relief Valve Pilot Assemblies Cleaned,Reworked & Satisfactorily Retested. Safety Valve Will Be Disassembled & Reworked | |
| 05000331/LER-1981-014, Forwards Updated LER 81-014/01X-1 | Forwards Updated LER 81-014/01X-1 | |
| 05000331/LER-1981-015, Updated LER 81-015/01T-1:on 810421,lower Crankshaft 14 Bearing Found Wiped on Journal Surface Similar to Problem Identified on Diesel 1G-31.Caused by High Temp.Bearing Replaced & Crankshaft Relapped | Updated LER 81-015/01T-1:on 810421,lower Crankshaft 14 Bearing Found Wiped on Journal Surface Similar to Problem Identified on Diesel 1G-31.Caused by High Temp.Bearing Replaced & Crankshaft Relapped | |
| 05000331/LER-1981-016, Updated LER 81-016/01T-1:on 810421,lower Crankshaft Thrust Bearing 13 & Adjacent Bearing 12 Found Wiped on Journal Surface.Caused by High Temp.Crankshaft Thrust Bearings Replaced & Crankshaft Relapped | Updated LER 81-016/01T-1:on 810421,lower Crankshaft Thrust Bearing 13 & Adjacent Bearing 12 Found Wiped on Journal Surface.Caused by High Temp.Crankshaft Thrust Bearings Replaced & Crankshaft Relapped | |
| 05000331/LER-1981-019-01, /01T-0:on 810526,found Tech Spec Surveillance Requirements for Determining River Water Supply Sys Pump TDH Not Being Met.Caused by Limits on Nameplate Data Being Too Stringent for Normal Operation | /01T-0:on 810526,found Tech Spec Surveillance Requirements for Determining River Water Supply Sys Pump TDH Not Being Met.Caused by Limits on Nameplate Data Being Too Stringent for Normal Operation | |
| 05000331/LER-1981-020, Forwards LER 81-020/01T-0 | Forwards LER 81-020/01T-0 | |
| 05000331/LER-1981-020-01, /01T-0:on 810527,primary Containment Integrity Breached When Inner & Outer Airlock Doors Were Open Simultaneously While H/P Technician Exited Drywell.Cause Unknown | /01T-0:on 810527,primary Containment Integrity Breached When Inner & Outer Airlock Doors Were Open Simultaneously While H/P Technician Exited Drywell.Cause Unknown | |
| 05000331/LER-1981-021-03, During Reactor Startup, Suppression Chamber to Drywell Vacuum Breaker Valve Cv 4237H Did Not Close After Torus Inerting.Caused by Pneumatic Cylinder Piston Sticking in mid-position | During Reactor Startup, Suppression Chamber to Drywell Vacuum Breaker Valve Cv 4237H Did Not Close After Torus Inerting.Caused by Pneumatic Cylinder Piston Sticking in mid-position | |
| 05000331/LER-1981-021, Forwards Updated LER 81-021/03X-1 | Forwards Updated LER 81-021/03X-1 | |
| 05000331/LER-1981-022, Forwards LER 81-022/03L-0 | Forwards LER 81-022/03L-0 | |
| 05000331/LER-1981-022-03, /03L-0:on 810607,during Testing,Reactor Core Isolation Cooling Turbine Repeatedly Tripped on Overspeed on Fast Starts.Caused by Upward Drift of Flow Controller FIC-2509 High Limit Setpoint.Setpoint Recalibr | /03L-0:on 810607,during Testing,Reactor Core Isolation Cooling Turbine Repeatedly Tripped on Overspeed on Fast Starts.Caused by Upward Drift of Flow Controller FIC-2509 High Limit Setpoint.Setpoint Recalibr | |
| 05000331/LER-1981-023, Forwards LER 81-023/03L-0 | Forwards LER 81-023/03L-0 | |
| 05000331/LER-1981-023-03, /03L-0:on 810611,during Surveillance Testing, Reactor Core Isolation Cooling Steam Line High Flow Pressure Differential Switch Pdis 2442,tripped at 100 Inches of Water.Caused by Instrument Drift.Switch Recalibr | /03L-0:on 810611,during Surveillance Testing, Reactor Core Isolation Cooling Steam Line High Flow Pressure Differential Switch Pdis 2442,tripped at 100 Inches of Water.Caused by Instrument Drift.Switch Recalibr | |
| 05000331/LER-1981-024, Forwards LER 81-024/03L-0 | Forwards LER 81-024/03L-0 | |
| 05000331/LER-1981-024-03, /03L-0:on 810616,drywell Equipment Drain Line Valve CV-3729 Did Not Give Fully Closed Indication During Testing.Caused by Seat Leakage in Solenoid Valve SV-3729. Solenoid Valve Replaced | /03L-0:on 810616,drywell Equipment Drain Line Valve CV-3729 Did Not Give Fully Closed Indication During Testing.Caused by Seat Leakage in Solenoid Valve SV-3729. Solenoid Valve Replaced | |
| 05000331/LER-1981-025-03, /03L-0:on 810616,RHR B Svc Water Pump Did Not Develop Required Discharge Pressure at Rated Flow.Caused by Normal Wear Creating Excessive Clearances Between Impeller & Casing Rings.Impellers Adjusted | /03L-0:on 810616,RHR B Svc Water Pump Did Not Develop Required Discharge Pressure at Rated Flow.Caused by Normal Wear Creating Excessive Clearances Between Impeller & Casing Rings.Impellers Adjusted | |
| 05000331/LER-1981-025, Forwards LER 81-025/03L-0 | Forwards LER 81-025/03L-0 | |
| 05000331/LER-1981-026-03, /03L-0:on 810615,containment Atmosphere Monitoring Sys B Was Found Operating W/O Sample Point Selected.Caused by Personnel Error.Particulate Radiation Element Replaced | /03L-0:on 810615,containment Atmosphere Monitoring Sys B Was Found Operating W/O Sample Point Selected.Caused by Personnel Error.Particulate Radiation Element Replaced | |
| 05000331/LER-1981-027-03, /03L-0:on 810620,radiation Monitor RM-4101A Failed Upscale.Caused by Component Failure.Equipment Drawer Replaced | /03L-0:on 810620,radiation Monitor RM-4101A Failed Upscale.Caused by Component Failure.Equipment Drawer Replaced | |
| 05000331/LER-1981-027, Forwards LER 81-027/03L-0 | Forwards LER 81-027/03L-0 | |
| 05000331/LER-1981-028, Forwards LER 81-028/03L-0 | Forwards LER 81-028/03L-0 | |
| 05000331/LER-1981-028-03, /03L-0:on 810703,during Control Room Panel Check, HPCI Pump Discharge Flow Indicating Controller FIC-2309 Found Indicating Low.Caused by Erroneous Indication of HPCI Flow Rate Due to Air Lock in HPCI Flow Indication Lines | /03L-0:on 810703,during Control Room Panel Check, HPCI Pump Discharge Flow Indicating Controller FIC-2309 Found Indicating Low.Caused by Erroneous Indication of HPCI Flow Rate Due to Air Lock in HPCI Flow Indication Lines | |
| 05000331/LER-1981-029-03, /03L-0:on 810701,during Testing,Containment Atmosphere Monitoring Sys (Cams) a Found to Be Operating W/O Sample Point Having Been Reselected.Cams B Inoperable Due to Testing.Caused by Personnel Error | /03L-0:on 810701,during Testing,Containment Atmosphere Monitoring Sys (Cams) a Found to Be Operating W/O Sample Point Having Been Reselected.Cams B Inoperable Due to Testing.Caused by Personnel Error | |
| 05000331/LER-1981-029, Forwards LER 81-029/03L-0 | Forwards LER 81-029/03L-0 | |
| 05000331/LER-1981-030, Forwards LER 81-030/03L-0 | Forwards LER 81-030/03L-0 | |
| 05000331/LER-1981-030-03, /03L-0:on 810701,torus Atmosphere Sampling Line Isolation Valve SV-8108A Would Not Close During Testing. Caused by Rust in Mechanical Portion of Solenoid,Impeding Proper Operation.Solenoid Dismantled & Cleaned | /03L-0:on 810701,torus Atmosphere Sampling Line Isolation Valve SV-8108A Would Not Close During Testing. Caused by Rust in Mechanical Portion of Solenoid,Impeding Proper Operation.Solenoid Dismantled & Cleaned | |
| 05000331/LER-1981-031, Forwards LER 81-031/03L-0 | Forwards LER 81-031/03L-0 | |
| 05000331/LER-1981-031-03, /03L-0:on 810820,reactor Core Isolation Cooling Suppression Pool Area Steam Leak Detection Temp Differential Switch TDS-2521C Found Tripping at Value Exceeding Tech Spec Limit.Caused by Instrument Drift.Switch Recalibr & Tes | /03L-0:on 810820,reactor Core Isolation Cooling Suppression Pool Area Steam Leak Detection Temp Differential Switch TDS-2521C Found Tripping at Value Exceeding Tech Spec Limit.Caused by Instrument Drift.Switch Recalibr & Tested | |
| 05000331/LER-1981-032-03, /03L-0:on 810812,containment Atmosphere Monitoring Sys a & B Found to Be Operating W/O Reselection of Sample Points,Resulting in Containment Atmosphere Not Being Monitored.Caused by Personnel Error.Design Review Initiated | /03L-0:on 810812,containment Atmosphere Monitoring Sys a & B Found to Be Operating W/O Reselection of Sample Points,Resulting in Containment Atmosphere Not Being Monitored.Caused by Personnel Error.Design Review Initiated | |
| 05000331/LER-1981-032, Forwards LER 81-032/03L-0 | Forwards LER 81-032/03L-0 | |
| 05000331/LER-1981-033, Forwards LER 81-033/03L-0 | Forwards LER 81-033/03L-0 | |
| 05000331/LER-1981-033-03, /03L-0:on 810817,reactor Core Isolation Cooling Sys Declared Inoperable to Replace Motor Operated Full Flow Test Valve MOV-2515.Caused by Pinhole Leak in Valve Body. Valve Hydrostatically Tested | /03L-0:on 810817,reactor Core Isolation Cooling Sys Declared Inoperable to Replace Motor Operated Full Flow Test Valve MOV-2515.Caused by Pinhole Leak in Valve Body. Valve Hydrostatically Tested | |