Proposed Change 173-1 YANKEE ATGMIC ELECTRIC COMPANY 2.C.15.1 j
1671 Worcester Road, Framingham, Massachusetts 01701 3
4
,Yauxes
@y,,ddd*
Ju17 8, 1981 United States Nuclear Regulatory Commission 4
JULl41931* 3 g,s,gg"oh Washington, D. C.
20555 a'
At ten tion : Office of Nuclear Reactor Regulation g
4 Re ferences : (a) License No. DPR-3 (Docket No. 50-29)
As (b) YAEC Letter to USNRC dated March 26, 1981 (FYR 81-52)
(c) YAEC Letter to USNRC dated June 6,1978 (WY2 78-48)
(d) YAEC Letter to USNRC dated June 1,1981 (LER 50-29/81-05/03L)
Sub je ct: Additional Technical Specification Char %cs - Supplement #1 tc Proposed Change #173
Dear Sir:
Pursuant to Section 50.59 of the Commission's Rules and Regu1ations, the Yankee Atomic Electric Company hereby requests the authorization to make the following additional Technical Specification changes to those submitted in Reference (b).
PROPOSED CHANGE:
Reference is made to the Yankee Plant Operating License No. DPR-3.
We propose to modify the license as follows:
1.
Replace page 2-6 with the attached revised page 2-6 (Note: This change supercedes the change submitted in Reference (b)).
2.
Replace pages 3/4 5-5 and 3/4 5-6 with the attached revised pages 3/4 5-5 and 5-6.
3.
Replace page 5-4 with the attached revised page 5-4.
REASON AND BASIS FOR CHOGE:
1.
We propose to adjust the high main coolant pressure trip setpoint to less than or equal to 2300 psig. This change is necessary to select a higher set pressure to preclude the possibility of inadvertent reactor trips due to surveillance testing of secondary side equipment and conditions resulting from normal plant load reductions.
2.
A plant modification is being implemented this outage to add dual contactors to SI MOV-46 (HPSI flow contral valve). This change allows operational flexibility to permit throttling operation of this 8107150010 810708 tb g
PDR ADOCK 05000029 P
U. S. Nacicar Regulatory Cosmiccion July 8,1981 Attantion: Office of Nuclear Reactor Regulatien Pega 2 valve from the centrol room without manual action to first connect power to the valve by closing the breaker at the motor control cen te r.
Dual contactors are used to prevent inadvertent operation of this valve by requiring two independent manual operator actions, as was similarly done and accepted in Proposed Change #160 (Reference (c)).
3.
Two hafnium control rods were replaced this outage as discuased in Reference (d). The Technical Specification changes are necessary to indicate all 24 control rods consist of silver, indium and cadmium absorber clad with Inconel.
SAFETY CONSIDERATION:
Based on the considerations contained herein, it is concluded that there is reasonable assurance that operation of the Yankee Rowe plant consistent with the proposed Technical Specifications will not endanger the healch and safety of the public. This proposed change has been reviewed by the Nuclear Safety Audit and Review Committee.
FEE DETERMINATION:
This proposed change is a supplement to those changes submitted in Reference (b) for which c $12,300 fee has already been submitted.
SCHEDULE OF CHANGE:
These changes to the Yankee Rowe Technical Specifications will be implemented upon Commission approval. A timely review and approval of this submittal consistent with our schedule for Core XV startup would be appreciated.
Core XV is scheduled to commence on or about July 24, 1981.
We trust that you will find this submittal satisfactory; however, should you desire additional information, please contact us.
Very truly yours, YANKEE ATOMIC ELECTRIC COMPANY N
W
(
L. H. Heider Vice President COMMONWEALTH OF MASSACHUSETTS)
)ss MIDDLESEX COUNTY
)
Then personally appeared before me, L. H. Heider, who, being duly sworn, did state that he is a Vice President of Yankee Atomic Electric Company, that he is duly authorized to execute and file the foregoing request in the name and on the behalf of Yankee Atomic Electric Company, and that the statements therein are true to the best of his knowledge and belief.
Ro'bert H. Groce Notary Public My Commission Expires September 14, 1984 j
l J