r

... =,

PPat TWO NORTH NINTH STREET, ALLENTOWN, PA.18101 PHONE: (215) 770 5151 NORMAN W. CURTIS Vice President Engineenng & Construction Nuclear 7745381 JUN 2 51981 gy ys

$/ d U _ II 9

N JUL 0 G 1921>

Mr. Boyce H. Grier, Director b p.s pos:Aa esmAA10s3 Region I h

N4M U.S. Nuclear Regulatory Commission

\\k

//

631 Park Avenue

%/P N

~

King of Prussia, PA 19406 SUSQUEHANNA STEAM ELECTRIC S'.

'JION IE BULLETIN 80-21 ER 100450 FILE 842-3 DOCKET NOS. 50-387 PLA-836 AND 50-388

Dear Mr. Grier:

The following information completes our response to IE Bulletin 80-21,

" Valve Yokes Supplied by Malcols Foundry Company, Inc."

IE Bulletin actions to be taken (CP) :

1.

Malcolm Foundry Company, Inc. supplied 156 yokes to Anchor-Darling Valve Company for use at Susquehanna SES of which 114 are on active valves.

In addition, the follcwing valve parts furnished to Anchor-Darling were also cast by Malcolm Foundry.

Part Total No.

No. on active valves Disk skirts 2

2 Disk skirt nute 4

4 Bevel gears 12 10 Bevel gear boxes 18 16 Bevel gear covers 4

4 Spur gears 8

8 Spur gear boxes 4

4 Spur gear covers 6

'6 Handwheel impactors 29 23 Handwheels 41 33 Handwheel inserts 2

0 No other valve vendors supplied valves to Susquehanna containing parts cast by Malcolm Foundry.

T.P'Il I

P E en N S Y L V A N 1 A P o W E R 8i LiG HT COMP ANY 8107070171 01062 PDR ADOCK 05000 7

G R

Mr. Boyce H. Grier Page 2 JUN 2 51981 2.

Not applicable to Susquehanna SES.

3.

All 156 valve yokes will be replaced.

In addition, the 2 disk skirts and 4 disk skirt nuts will also be replaced.

The remaining parts will not be replaced since they were specified to be cast from commercial steel and are not essential to valve safety functions. All defective parts are scheduled for replacement by October, 1981, in accordance with Bechtel NCR 5980.

Estimated manpower expended on IE Bulletin 80-21:

a) Report preparation and review 500 manhours

5) Corrective actions 7300 manhours Total 7800 manhours Very truly yours, h

1

--i M

N. W. Curtis Vice President-Engineering & Construction-Nuclear RMH/mks cc: Director Division of Reactor Construction Inspection Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 l

Mr. G. G. Rhoads l

U.S. Nuclear Regulatory Commission l

P.O. Box 52 j

Shickshinny, PA 18655 l

Mr. L. D. Narrow U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 i

l i

1 I

...