ADMINISTRATIVE CONTROLS PROCEDURES AND PROGRAMS (Continued) f.

Radioloaical Envi onmental Monitorina Proaram (Continued) 3)

Participation in a Interlaboratory Comparison Program to ensure that. independent checks on the precision and accuracy of the measurements of radioactive materials in environmental sample matrices are performed as part of the quality assurance program for environmental monitoring.

g.

Containment Leakaae Rate Testine Jrttrm I

A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50, Appendix J, Option B, as modified by approved exemptions.

This program shall be in accordance with the guidelines contained in Rtatlatory Guide 1.163, " Performance-Based Containment Leak-Test Program," dated September 1995.

The peak calculated containment internal pressure for the design basis loss of coolant accident, P, is 48.1 psig.

The maximum allowable containment leakage rate,- L,, at P,, shall be 0.20% of the containment air weight per day.

Leakage rate acceptance criteria are:

Containment leakage rate acceptance criterion is s1.0 L,.

a.

During the first unit startup following testing in accordance with this program, the leakage rate acceptance a teria are s0.60 L 1

., for Type A tests;, for the Type B and C tests and s0.75 c

s b.

Air lock testing acceptance criteria are:

1)

Overall air lock leakage rate is 50.05 L, when tested at 2P,;

2)

For each door, leakage rate is so.005 L, when pressurized to 210 psig.

The provisions of Technical Specification 4.0.2 do not apply to the test frequencies in the Containment Leakage Rate Testing Program.

The provisions of Technical Specification 4.0.3 are applicabie to the Containment Leakage Rate Testing Program.

h.

Diesel Fuel Oil Testino Proaram A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil. The program shall include sampling and testing requirements, and acceptance criteria, in accordance with the applicable ASTM Standards. The purpose of the program is to establish the following:

CALLAWAY - UNIT 1 6-19 Amendment No. 27,50,103,111,112 9609090204 960004 CF-ADDCK 05000483 CF

l ADMINISTRATIVE CONTROLS 1

PROCEDURES AND PROGRAMS (Continued) h.

Diesel Fuel Oil Testina Proaram (Continued) i 1.

Acceptability of new fuel oil for use prior to addition to storage tanks by determining that the fuel oil has:

a.

an API gravity or an absolute specific gravity within

limits, b.

a flash point within limits for ASTM 2D fuel oil, c.

a kinematic viscosity within limits for ASTM 2D fuel

oil, d.

a water and sediment content within the limits for ASTM 20 fuel oil; 2.

Other properties for ASTM 2D fuel oil are within limits within 30 days following sampling and addition of new fuel oil to storage tanks; 3.

Total particulate concentration of the stored fuel oil is

<10 mg/ liter when tested every 31 days based on applicable ASTM D2276 Standards; and i.

Emeroency Diesel Generator Reliability Proaram An emergency diesel generator reliability program that establishes the requirements ad guidelines for emergency diesel generator reliability, availability, and monitoring.

The program shall include the following:

1.

Emergency diesel generator reliability performance goals (target reliability) based upon the station blackout coping assessment. Target reliability goal monitoring is accomplished through monitoring methods that are based upon tho::e described in Appendix D of NUMARC 87-00, 2.

Measures to ensure detailed root cause analysis of emergency diesel ger.erator failures is performed and effective corrective actions are taken in response to failures, 3.

Implementation of an emergency diesel generator preventive maintenance program that is consistent with the Maintenance Rule, and 4.

Monitoring of emergency diesel generator availability and performance parameters to ensure the target reliability is met or exceeded.

6.8.5 The following programs, relocated from the Technical Specifications to FSAR Chapter 16, shall be implemented and maintained:

l a.

Explosive Gas and Storace Tank Radioactivity Monitorina Procram This program provides controls for potentially explosive gas l

mixtures contained in the WASTE GAS HOLDUP SYSTEM, the quantity of radioactivity contained in gas storage tanks, and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks.

l CALLAWAY - UNIT 1 6-19a Amendment No. 103,111,112

I

!c ADNINISTRATIVE CONTROLS PROCEDUREE_RELEBQfiB8MS (Continued) l

'a.

Exnlosive Gas and Storace Tank Radioactivity Monitorina Proaram (Continued)

The program shall include:

1.

The limits for concentrations of hydrogen and oxygen in the WASTE GAS HOLDUP SYSTEM and a surveillance program to ensure the limits are maintained.

2.

A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of 20.5 rem to a MEMBER OF THE PUBLIC at the nearest SITE BOUNDARY in the event of an uncontrolled release of the tanks' contents, consistent with' Branch Technical Positici ETSB 11-5, " Postulated Radioactive Releases due to Waste Gas System Leak or Failure," in NUREG-0800, July 1981.

l 3.

A surveillance program to ensure that the quantity of l

radioactivity contained in the following outdoor liquid I

radwaste tanks, that are not surrounded by liners, dikes, or walls capable of holding the tanks' contents and that do not have tank overflows and surrounding area drains connected to the liquid radwaste system, is less than the amount that would result in concentrations less than the limits of 10 CFR Part 20.1 -20.602, Appendix B (redesignated at i

56FR23391, May 21, 1991) at the nearest potable water supply and the nearest surface water supply in an UNRES1RICTED AREA, in the event of an uncontrolled release of the tanks' contents:

I a.

Reactor Makeup Water Storage Tank, b.

Refueling Water Storage Tank, c.

Condensate Storage Tank, and d.

Outside temporary tanks, excluding demineralizer vessels and the Ifner being used to solidify radioactive waste.

j The provisions of Specifications 4.0.2 and 4.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.

b.

Reactor Coolant Pumo Flywheel Inspection Proaram Each reactor coolant pump flywheel shall be inspected per the j

recommendations of Regulatory Position C.4.b of Regulatory Guide j

1.14, Revision 1, dated August 1975.

c.

Containment Tendon Surveillance Proaram l

This program provides controls for monitoring tendon performance, including the effectiveness of the tendon corrosion protection medium, to ensure containment structural integrity. The program i

shall include baseline measurements prior to initial plant CA LLAWAY - UNIT 1 6-19b Amendment No. 103,111,112 l

i

_ _~

-_