Forwards Application for Amend to License NPF-3,revising post-accident Monitoring Tech Spec Tables 3.3-10 & 4.3-10 & Refueling Operations
ML20006F147
Person / Time
Site: Davis Besse 
Issue date: 02/02/1990
From: Shelton D
TOLEDO EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20006F148 List:
References
1733, TAC-M75236, NUDOCS 9002270205
Download: ML20006F147 (2)


Text

9'

.(...

+.-

of

-1 TOLEDO l

EDISON J

A Cs wiar Energy Compny DONALD C. SHELTON vo. or

+,u=.r Docket Number 50-346 5""

License Number NPF-3

. Serial Number 1733 February 2, 1990 United States Nuclear Regulatory Commission l

Document Control Desk Vashington,:D. C. 20555 i

Subject s ~ License Amendment Application to Revise the Post-Accident Monitoring Specification Tables 3.3-10 and 4.3-10 and Refueling Operations Instrementation Specification (TAC Number M75236) v Gentlemen:

The enclosed application requests that the Davis-Besse Nuclear Power Station (DBNPS), Unit Number 1 Operating License, Appendix A, Technical Specifications be revised to' reflect the changes attached. The proposed changes involve Technical Specification (TS) 3/4.3.3.6, Post-Accident Instrumentation, Table 3.3-10, Post-Accident Monitoring Instrumentation, Table.4.3-10, Post-Accident Monitoring Instrumentation Surveillance Requirements, and TS 3/4.9.2,

. Refueling Operations-Instrumentation.

The DBNPS has been using the excore neutron flux monitors supplied with'the

' Babcock and Wilcox (B&V) nuclear instrumentation system to meet both TS 3/4.9.2 and TS 3/4.3.1.1,. Reactor Protection System Instrumentation, Table

,3.3-1 and 4.3-1, Item 11 (Source Range, Neutron Flux and Rate - Startup and Shutdown). However, the B&W-supplied nuclear instrumentation system is not environmentally qualified.

Two excore neutron. flux monitors qualified to meet the requirements of Regulatory Guide 1.97, " Instrumentation for Light-Water-Cooled Nuclear Power Plants to Assess Plant and Environs Conditions During and Following an Accident", were installed during the fifth refueling outage at the DBNPS and vill be available to be used to comply with

\\.

TS 3/4.3.3.6 following the sixth refueling outage and also with TS 3/4.9.2

)-

during the sixth refueling outage. This request proposes the addition of

" neutron flux (vide range)" and " neutron flux (source range)" to Tables 3.3-10 and 4.3-10 to reflect the appropriate surveillance requirements for the new monitors for demonstrating operability.

Additionally this request proposes TS 3/4.9.2 be changed to require calibration of the neutron flux monitors prior to entry into Mode 6 in order to allow either the new monitors or the existing s~, u ", ".ity g,t,o be,u, sed to comply with this specification.

9002270205 900202 d

a PDR ADOCK 05000346 d

p0J e

nu^

l\\

THE TOLEDO EDISON COMPANY EDISON PLAZA 300 MADISON AVENUE TOLEDO OHIO 43652

t

.a

-Dock 3t Nurb2r 50-346.

License Number NPF-3

Seriil' Number 1733-Page 2 J

-Toledo Edison requests that this amendment, which is associated with (6

-activities to be performed during the sixth refueling outage, be issued by the NRC by Hay.1,-1990.

Should further-information be required, please contact'Mr.'R. V. Schrauder, Nuclear Licensing Manager, at (419) 249-2366.