Exemption from 10CFR50,App R,Section Iii.J Emergency Lighting Requirements
ML20006E384
Person / Time
Site: Oyster Creek
Issue date: 02/12/1990
From: Varga S
Office of Nuclear Reactor Regulation
To:
GENERAL PUBLIC UTILITIES CORP.
Shared Package
ML20006E380 List:
References
NUDOCS 9002230036
Download: ML20006E384 (3)


Text

^~

~

~

~

^~

c,

3.

AC

'b

,, z i

7590-01 UNITED STATES NUCLEAR REGULATORY COMMISSION i

Inlthe Matter of (GPUNUCLEARCORPORATIONAND Docket No. 50-219 3

JERSEY-CENTRAL POWER & LIGHT COMPANY) j 1(Oyster Creek Nuclear Generating' Station)-

EXEMPTION i

I.

The GPU Nuclear Corporation and Jersey Central Power & Light Company (GPUN/

the licensee) are the holders of Provisional Operating License'No. DPR-16, which authorizes operation of the Oyster Creek Nuclear Generating Station, (the facility) at steady state reactor core power levels not in excess of 1930 megawatts thermal. The license provides, among other things, that Oyster Creek Nuclear Generating Station is subject to all rules, regulations, and Orders of the Commission now or hereafter in effect.

Theplantisboilingwaterreactor(BWR)locatedatthelicensee'ssite t

in Ocean County, New Jersey.

)

II.

On November 19, 1980, the NRC published a revised Code of-Federal Regulations, Section 10 CFR 50.48 and a new Appendix R to 10 CFR Part 50 regarding fire l

,M

_ protection features of nuclear power plants. The revised Section 50.48 and o,

Appendix R became effective on February 17, 1981.Section III of Appendix R tvES l g o.-

~containsfifteen(15) subsections,letteredAthrough0,eachofwhichspecifies 6

requirements for a particular aspect of the fire protection features at a j

nuclear power plant. One of these fifteen subsections, III.J. is the subject too y<

of this exemption request.

Specifically,Section III.J requires emergency n

88

. lighting units of 8-hour capacity be provided for all areas needed for operation o n.e, ll Jof safe shutdown equipment and for access and egress routes thereto.

L

Lp

)

III.

t i

By letter dated November 24, 1986, the licensee requested an exemption

{

from the requirements of Section III.J of Appendix R to 10 CFR Part 50 to move 2

into the control room the d.c. power source (batteries or battery / charges l

units) for the control room emergency lights. The basis for the requested exemption is that two lighting systems are installed in the control room.

Each system has its own independent power supply.

In addition, the power supplies and electrical circuits to the two lighting systems are so separated that no single fire outside the control room will damage both. This arrangement assures continuous lighting in the control room in the event of any postulated fire occurring in the plant.

The staff has reviewed the licensee's request and the supporting technical information contained in the licensee's Novenber 24, 1986 letter.

L The staff agrees with GPU Nuclear Corporation's conclusion that the existing two lighting systems with independent and separate power supplies and circuits provided for the control room are fully acceptable. The staff also agrees that the installation of individual 8-hour capacity battery powered emergency lighting units in the control room would not significantly improve fire safety in the plant.

IV.

Accordingly, the Comission has determined that, pursuant to 10 CFR 50.12, this exemption is authorized by law, will not present an undue risk to the public health and safety, and is consistent with the comon defense and security.

.The Comission has further determined that special circumstances, as set forth in 10 CFR 50.12(a)(2)(ii), are present justifying the exemption, namely that the application of the regulation in the particular circumstances is not necessary to achieve the underlying purpose of the rule.

Accordingly, the Comission hereby grants an exemption as described in Section III above from the require-ments of Section III.J of Appendix R to 10 CFR part 50.

~:

g s.

k

'(

E Pursuant to 10 CFR 51.32, the Commission has determined that the granting

)

1 of this exemption will have no significant impact on the environment

{

( 55 FR 4497

).

This exemption is effective upon issuance.

l FOR THE NUCLEAR REGULATORY COMMISSION

%mu aut Division of Reactor Proj'

- I/II Office of Nuclear Reactor egulation Dated at Rockville, Maryland this 12th day of February, 1990 L