UNITED STATES
["
jf 3 NUCLEAR REGULATORY COMMISSION l
g
,3
-[
WASH 6NGTON,0 C.70666 t
- ...+$
I ARIZONA PUBLIC SERVICE COMPANY. ET AL.
DOCKET NO. STN 50-529 t
PALO VERDE NUCLEAR GENERATING STATION. UNIT NO. 2 l
AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 32 License No. NPF-51 1.
The Nuclear Regulatory Comission (the Comission) has found that' A.
The application for amendment, dated December 29 1989, as i
supplemented January 3,1990 by the Arizona Pub 1Ic Service Company (APS) on behalf of itself and the Salt River Project J
Agricultural Improvement and Power District, El Paso Electric Company, Southern California Edison Company, Public Service j
Company of New Mexico, Los Angeles Department of Water and 1
Power andSouthernCaliforniaPublicPowerAuthority(licensees),
comp 1IeswiththestandardsandrequirementsoftheAtomic j
Energy Act of 1954, as amended (the Act) and the Comissio3's regulations set forth in 10 CFR Part 1; B.
The facility will operate in conformity with the application, the provisions of Act, and the regulations of the Comission; C.
Thereisreasonableassurance(1)thattheactivitiesauthorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; 1
E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the enclosure to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-51 is hereby amended to read as follows:
%2QQ@$ [
{
P-
i 2
t (2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised i
through Amendment No. 32, and the Environmental Protection Plan contained in Appendix B, are hereby incorporated into this license.
l APS shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
l 3.
This license amendment is effective as of the date of issuance.
FOR THE NUCLEAR REGULATORY C0m!SSION i
wMi."/iiwk 2
Charles M. Trammell, Acting Director Project Directorate V Division of Reactor Projects !!I, IV, Y and Special Projects Office of Nuclear Reactor Regulation j
Enclosure:
I Changes to the Technical Specifications
]
Date of Is:;uance: February 2, 1990 1
~
l ENCLOSURE TO LICENSE AMENDMENT AMENDNENT NO. 32 TO FACILITY OPERATING LICENSE NO. NPF-51 DOCKET NO. STN 50-529 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page.
The revised page is identified by amendment number and contain vertical line indicating the area of change.
Remove Page insert.Page 3/4 1-22 3/4 1-22
.i, t
REACTIVITY CONTROL SYSTEMS LIMITING CONDITION FOR OPERATION (Continued)
ACTION:
(Continued) b)
The SHUTDOWN MARGIN requirement of Specification 3.1.1.2 is determined at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
Otherwise, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
d.
With one full-length CEA Inoperable due to causes other than addressed by ACTION a., above, but within its above specified align-ment requirements, operation in MODES 1 and 2 may continue pursuant to the requirements of Specification 3.1.3.6.
With one part-length CEA inoperable and inserted in the core, e.
operation may continue provided the alignment of the inoperable part length CEA is maintained within 6.6 inches (indicated position) of all othe~ part-length CEAs in its group and the CEA is maintained pursuant to the requirements of Specification 3.1.3.7.
i SURVEILLANCE REQUIREMENTS 4.1.3.1.1 The position of each full-length and part-length CEA shall be deter-mined to be within 6.6 inches (indicated position) of all other CEAs in its group at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> except during time intervals when one CEAC is inoperable or when both CEACs are inoperable, then verify the individual CEA positions at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, i
4.1.3.1.2 Each full-length CEA not fully inserted and each part-length CEA i
which is inserted in the core shall be determined to be OPERABLE by movement of at least 5 inches in any one direction at least once per 31 days.*
l l
l I
i
- With the exception that CEAs 27 and 41 are exempt from this surveillance requirement until restart from the second refueling outage.
J PALO VERDE - UNIT 2 3/4 1-22 AMENDMENT NO. 32