Notice of Violation from Insp on 891116-1231.Violations Noted:Tape Splices for Feedwater Containment Isolation Valves Lacked Okonite T-95/35 Tape & Output Leads from Transmitter Reversed When Reconnected
ML20006D470
Person / Time
Site: Arkansas Nuclear  
Issue date: 02/01/1990
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20006D469 List:
References
50-313-89-45, 50-368-89-45, NUDOCS 9002130286
Download: ML20006D470 (2)


Text

_ __

],: ],,

I APPENDIX A o

NOTICE OF VIOLATION Arkansas Power & Light Company Dockets: 50-313 i

50-368 r

Arkansas Nuclear One, Units 1 & 2 Licenses: DPR-51 NPF-6 During an NRC inspection conducted November 16 through December 31, 1989, violations of the NRC requirements were identified.. The violations involved

. failure to maintain the environmental qualification of certain plant equipment and; failure to comply with approved station procedures.

In accordance with the

" General. Statement of Policy and Procedure for NRC Enforcement Actions " 10 CFR Part 2,' Appendix C (1989)-(Enforcement Policy), the violations are listed below:

~ A.

Failure to Prapare Splices in Accordance with a Drawing 10 CFR 50, Appendix B, Criterion V, requires that licensees activities affecting quality shall be prescribed by documented instructions, procedures, or drawings... and shall be accomplished in accordance with these instructions, procedures, or drawings.

To meet the requirements of 10 CFR, Appendix B, in preparing tape splices for motor operated valves, the configuration for an electrical connection splice was detailed in AP&L Drawing E-2052, Sheet 37E. This drawing establishes acceptable configurations for environmentally qualified tape splices and requires the use of T-95/35 tape.

-Contrary to the requirements of Drawing E-2052, Sheet 37E, the tape s lices for Feedwater Containment Isolation Valves CV-2630 and CV-2680

-(prequired to be environmentally qualified) had no Okonite T-95/35 tape installed.

This is a Severity Level IV violation.

(SupplementI)(313/8945-01)-

.)

' B.

Failure to Follow Procedural Requirements 10 CFR Part 50, Appendix B, Criteria V states, in part, " Activities l

affecting quality shall be prescribed by documented instructions, procedures, or drawings, of a type appropriate to the circumstances and shall be accomplished in accordance with these instructions, procedures, or drawings...."

Licensee Procedure 1025.003, " Conduct of Maintenance," provides requirements for the control of work activities.

Specifically, paragraphs 3.8 and 4.3A require that lifted leads be marked to aid in retermination and that independent verification of the retermination be performed.

In addition, paragraphs 6.27.6 and 6.27.7 provide measures for the control of procedures, including signoffs, when working in a contaminated area.

y o o :u 3 t 2 s%

qcoto' i

70 L BDOC K 050 0 05IE

,l cSL PD C

\\Tv

/

yy

._ -i Contrary to the above, the licensee failed to comply with procedural requirements during. maintenance activities in the three examples discussed i

below:"

l 1.

.During calibration of the Unit 2 feedwater control system, various electrical leads were lifted. Subsequent inspections of a feedwater

. control cabinet identified a loose electrical lead. A review of the work history indicates that no independent verifications of electrical lead reterminstions were performed.

2.

On November 27, 1989, while testing Unit 1 Low Pressure Injection Flow Transmitter PDT-1402, the output leads from the transmitter were lifted then later retenninated.

Subsequent testing revealed that the 1

. output leads were reversed when reconnected. When the output leads I

were retenninated, an independent verification was not performed.

]

3.

On' November 27, 1989, while observing the reassembly of the motor

-l operator for Unit 1 High Pressure Injection Valve CV-1220, the a

inspector noted that'none of the removed or restored signoffs on the i

.i

" Lifted Lead Data Sheet" had been made. The licensee's craftsman?

stated that all of the signoffs would be made after the work was t

4 completed and the worker had exited the contaminated area. This i

method of completing signoffs is contrary to the. requirements of-Administrative Procedure 1025.003.

The above. examples constitute a Severity Level IV violation.

(SupplementI)

/

(313/8945-02;368/8945-02).

Pursuant to the provisions of 10 CFR 2.201 Arkansas Power & Light Company-is hereby requiredito submit to this office within 30 days of the date of. the.

letter transmitting this Notice, a written statement or explanation in reply, including for'each violation:.(1) the reason for the violation if admitted, the corrective steps which have been taken and the results achieved, the corrective steps which will be.taken to avoid further violations, and the date when full compliance will be achieved.. Where good cause is shown, consideration will'be given to extending the. response time.

Dated at Arlington, Tex s, this7 /# day of 7 1990 L