ML20005C080

From kanterella
Jump to navigation Jump to search
Forwards LERs 81-060/03L-0,81-062/03L-0 & 81-063/03L-0
Date released: 01/19/2020 Download: ML20005C080


LER 81-063/03L-0:on 811019,charging Pump Svc Water Pump 1-SW-P-10B Found to Have Zero Discharge Pressure Because of Loss of Suction to Pump.Caused by Increased Use of Svc Water by Chillers.Flow to Chillers Throttled
ML20005C095
Person / Time
Site: Surry 
Issue date: 10/06/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20005C095 (2)
LER 81-062/03L-0:on 811017,radiation Monitor RI-CC-105 Failed to Give Indication.Caused by Broken Wire Located on Detector Probe.Wire Reconnected
ML20005C090
Person / Time
Site: Surry 
Issue date: 11/06/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20005C090 (2)
LER 81-060/03L-0:on 811013,outlet Valve from Chemical Addition Tank Would Not Cycle Electrically.Caused by Motor Operation Overload Protection Thermalling Open While Attempting to Cycle Valve,Due to Overly Tightened Valve
ML20005C083
Person / Time
Site: Surry 
Issue date: 11/06/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20005C083 (2)
Forwards LERs 81-060/03L-0,81-062/03L-0 & 81-063/03L-0
ML20005C079
Person / Time
Site: Surry 
Issue date: 11/06/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20005C079 (1)