ML20005A046

From kanterella
Jump to navigation Jump to search
Forwards LER 81-051/03L-0
Date released: 01/19/2020 Download: ML20005A046


LER 81-051/03L-0:810607,turbine Failed to Trip at Less than or Equal to 5,000 Rpm During Testing.Caused by Broken Turbine Trip Ball,Scored Trip Piston & Out of Calibr Diaphragm Oil Control Valve.Ball Replaced & Valve Cleaned
ML20005A053
Person / Time
Site: Hatch 
Issue date: 06/23/1981
From: Coggin C
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20005A053 (2)
Forwards LER 81-051/03L-0
ML20005A045
Person / Time
Site: Hatch 
Issue date: 06/23/1981
From: Manry M
GEORGIA POWER CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20005A045 (1)