Revised Tech Spec Table 2.2-1 & Revised Supporting Bases Paragraph 2.2.2
ML20004E849
Person / Time
Site: Arkansas Nuclear 
Issue date: 06/10/1981
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20004E848 List:
References
NUDOCS 8106150385
Download: ML20004E849 (2)


Text

'

TABLE 2.2-1 (Continued) g l

REACTOR PROTECTIVE INSTRUMENTATION TRIP SETP0 INT LIMITS 5

M

~

G]

FUNCTIONAL UNIT T7I SETPOINT ALLOWABLE VALUES O

E 9.

Local Power Density - High 1 20.3 kw/ft (5) 1 20.3 kw/ft (5) g

b
10. ONBR - Low

> 1.24 (5) (6) l@

~> 1.24 (5) (6) ll

11. Steam Generator Level - High 1 93.7% (4)

$ 94.589% (4) l TABLE NOTATION i

(1) Trip may be manually bypassed above 10-4% of RATED THERMAL POWER; bypass shall be automatically removed when THERMAL POWER is 1 10-4% of RATED THERMAL POWER.

'?

(2) Value may be decreased manually, to a mir.imum value of 100 psia, during a planned reduction in l

1 pressurizer pressure, provided the margin between the pressurizer pressure and this value is maintained at 5 200 psi, the setpoint shall be increased automatically as pressurizer pressure is increased until the trip setpoint is reached.

Trip may be manually bypassed below 400 psia; bypass shall be automatically removed whenever pressurizer pressure is > 500 psia.

l (3) Value may be decreased manually during a planned reduction in steam generator pressure, provided l

the margin between the steam generator pressure and this value is maintained at < 200 psi; the 1

setpoint shall be increased automatically as steam generator pressure is increased until the trip setpoint is reached.

(4) % of the distance between steam generator upper and lower level instrument nozzles.

(5) As stored within the Core Protection Calculator (CPC).

Calculation of the trip setpoint includes i

measurement, calculational gnd processor uncertainties, and dynamic allowances. Trip may be I

manually bypassed below 10-4% of RATED THERMAL POWER; bypass shall be automatically removed when THERMAL POWER is > 10-4% of RATED THERMAL POWER.

(6) The minimum allowable value of the addressable constant BERR1 in each OPERABLE CPC channel is 1.112.

Upon NRC approval of the Statistical Combination of Uncertainties Methodology as described in CEN-139(A)-P, the minimum allowable value of BERR1 is 1.055.

4 a

Y

SAFETY LIMITS AND LIMITING SAFETY SYSTEM SETTINGS BASES a.

RCS Cold Leg M perature-Low

> 465 F b.

RCS Cold Leg Temperature-High 7 605 F 0

c.

Axial Shape Index-Positive liot more positive than +0.6 d.

Axial Shape Index-Negative Not more negative than -0.6 e.

Pressurizer Prassure-Low

> 1750 psia f.

Pressurizer Pressure-High 7 2400 psia g.

Integrated Radial Peaking Factor-Low s 1.28 h.

Integrated Radial Peaking Factor-High i4.28

i. Quality Margin-Low

>0 Steam Generator Level-High The Steam Generator Level-High trip is provided to protect the turbine from excessive moisture carry over.

Since the turbine is automatically tripped when the reactor is tripped, this trip provides a reliable means for providing protection to the turbine from excessive moisture carry over. The trip's setpoint does not correspond to a Safety Limit and no credit was taken in the accident analyses for operation of this trip.

Its functional. capability at the specified trip setting is required to enhance the overall reliability of the Reactor "rotection System.

2.2.2 CPC Addressable Constants The Core Protection Calculator (CPC) addressable constants are provided to allow calibration of the CPC system to more accurate indications such as calorimetric measurements for power level and RCS flow rate and in core detector signals for axial flux shape, radial peaking factors and CEA deviation penalties. Other CPC addressable constants allow penalization of the calculated DNBR and LPD values based on measurement uncertainties or inoperable equipment.

Administrative controls on changes and periodic checking of addressable constant values (See also Technical Specification 2.2.1.1 and 6.8.1) ensures that in-advertent misloading is unlikely. The methodology for determination of CPC addressable constant values is described in APSL letter 2CAN058113 dated May 26, 1981.