LER 81-035/03L-0:on 810511,containment Isolation Valve CCW-MOV-3052,was Declared Inoperable When Valve Position Indication Was Lost.Caused by Blown Control Power Fuse.Fuse Replaced
ML20004E199
Person / Time
Site: Farley 
Issue date: 06/05/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004E199 (1)
LER 81-034/03L-0:on 810509,train a Refueling Water Storage Tank Level Indicator Failed Low.Cause Undetermined. Investigation Underway.Problem Has Not Recurred
ML20004E197
Person / Time
Site: Farley 
Issue date: 06/05/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004E197 (1)
LER 81-030/03L-0:on 810505,B1F Sequencer Failed to Meet Time Requirements for Picking Up Step 6 During Testing. Caused by Agastat Timer Being Out of Adjustment.Timer Setpoint Adjusted