ML20004C634

From kanterella
Jump to navigation Jump to search
Forwards LER 81-020/03L-0
Date released: 01/18/2020 Download: ML20004C634


LER 81-020/03L-0:on 810506,during Diesel Generator Redundant Start Test (EMI-3),D Engine Left Bank Air Start Motors Would Not Develop Min Rotational Speed.Caused by Broken Vane.Air Starting Motors Replaced
ML20004C638
Person / Time
Site: Browns Ferry 
Issue date: 05/29/1981
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004C638 (2)
Forwards LER 81-020/03L-0
ML20004C633
Person / Time
Site: Browns Ferry 
Issue date: 05/29/1981
From: Green H
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004C633 (1)