ML20003H396

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in IE Insp Repts 50-295/81-01 & 50-304/81-01.Corrective Actions:Met W/Shift Engineers & Emphasized Need to Complete Operating Log Books
ML20003H396
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 04/08/1981
From: Abel J
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20003H395 List:
References
NUDOCS 8105050763
Download: ML20003H396 (2)


Text

.

One First Nat onat Ptara CNcago til ncis Commonwealth Edison S

Adcress Rep:y to-Post Off ce Box 767 Chicago. lilinois 60690 April 8, 1981 Mr. James G. Keppler, Director Directorate of Inspection and Region III Enforcement U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Zion Station 'Jnits 1 and 2 Response to IE Inspection Report Noc. 50-295/81-01 and 50-304/81-01 BC Docket Nos. 50-295/204 Reference (a):

March 16, 1981 letter from R.

F. Heishman to C. Reed

Dear Mr. Keppler:

Reference (a) contained the results of inspections conducted by Messrs. J. E. Kohler and J.

R. Waters on January 1 through February 27, 1981, of activities at Zion.

During that inspection certain activities appeared to be in non-compliance with NRC requirements.

Attachment A to this letter contains Commonwealth Edison's response to the Notice of Violation.

To the best of my kTowledge and belief the statements contained in the attachment are true and correct.

In some respects these statements are not baset on my personal knowledge but upon information furnishea by other Commonwealth Edison employees.

Such information has been reviewed in accordance with Company practice and I believe it to be reliable.

Please acdress any questions concerning this matter to this office.

Very truly yours,

/

I S. Abel Director of Nuclear Licensing cc:

Resident Office - Zion SUBSCRIBED and SWORN to da 1981 rs ne w

'Not'any'Public 2141B 810505014205 APR I 3 1981

Y Attachment A Response to Notice of Violation Violation As a result of the inspection conducted on January 1,

1981 to February 27, 1981, and in accordance with the Interim Enforcement Policy 45 FR 66754 (October 7, 1980), the following violation was identified:

Technical Specificatior 6.2.A states in part that aetaileo written procedures shall be preparea, approved and achered to...

Cortrary to the above, Zion Administratove Procedure 10-52-2, Operating Log Books, was violated on February 12, 1981 when nuclear station operator and shift engineer log books did not incluce an entry regarding significant reactor coolant system leakage that was occurring on Zion Unit 2.

Corrective Action Taken and the Results Achieved:

The week immeciately following the Senior Resiaent Inspector's exit interview, Station Operating management held a meeting with the Shift Engineers to review the events of February 12 ano the Inspector's related concerns.

At this meeting, the requirements of ZAP 10-52-2, Operating Log Books, were discussed and it was emphasizec tht the SE/SF Turnover Checklist was designea to supplement and not to substitute for the information in the Shift Engineer Log.

Operating managment's review of the logs since that meeting has shown that the requirements of ZAP 10-52-2 are being followec.

Corrective Action Taken to Avoid Further Noncompliance:

The content of ZAP 10-52-2, Operating Log Books, has been reviewea and it is current and sufficient.

As regards operator detection of increases in racioactive release rates, the release path monitor recorders are located behind the main control board and, as noted in the Inspection Report, the release on February 12 was well below the alarm setpoint for the applicable monitor.

The operator at the controls (at the front of the control board) would check these monitors in response to a front panel alarm.

To facilitate detection, Station Operating management has in effect a Standing Oraer instructing the operator to mark the recorder chart for changes in release rates, including those that do not reacn an alarm point.

The recorder charts are also reviewed t shift supervision on a ranoom basis during the shift.

Date of Full Compliance:

The licensee is in compliance at the present time.

t