ML20003G439

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-24, Prevention of Damage Due to Water Leakage Inside Containment (Oct 17,1980 Indian Point 2 Event). Lists Interim Measures Being Implemented to Ensure Leakage Into Containment Will Not Go Undetected
ML20003G439
Person / Time
Site: Fort Calhoun 
Issue date: 01/05/1981
From: William Jones
OMAHA PUBLIC POWER DISTRICT
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
IEB-80-24, NUDOCS 8104290429
Download: ML20003G439 (2)


Text

.

f lh p-x. Al' Omaha Public Power District 1623 HARNEY a O M AM A, NESRASKA 68102 s TELEPHONE 536-4000 AREA CODE 402 January 5, 1981 To ADM/DMB:

PDR LPDR Mr. K. V. Seyfrit, Director NSIC U. S. Nuclear Regulatory Commission QQM/ TID office of Inspection and Enforcement ADM/R56 Region IV yr. g g,;,

611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76011

- -. ~.

Reference:

Docket No. 50-285

Dear Mr. Seyfrit:

Omaha Public Power District received IE Bulletin 80-24, dated November 21, 1980, regarding prevention of damage due to water leakage inside containment. The bulletin identified three separate actions to be taken by licensees.

The first two actions are not applicable to Fort Calhoun, since they apply only to plants with open cooling water systems in containment.

The District's response to action 3 is attached.

Approximately 16 manhours were expended in conducting the review and preparing the reports required by the bulletin.

Sincerely, fh-W. C. Jones Divisi'on Manager Production Operations WCJ/KJM/TLP:jem Attachment k

SER24Jgg7 2

l cc:

OISE - Washington g

', u.s, %,y, W on LeBoeuf, La=b, Leiby & MacRae

^

'*wss 8

l/h l

/ 4 P

Subscribed and sworn to before me m

this a m day of,%..~ r 1981.

j

/ /a i

A saninat auer-im.....

--e m.

'E

.L T. GLEASON

//

Notary Public W Cm Emo.Wy28.1982 81042fl0 M Q

4 l

Action to be Taken 3.

For plants with closed cooling water systems inside containment provide a summary of experiences with cooling water system leakage into containment.

Response

At the Fort Calhoun Station, the Component Cooling Water (CCW) system provides all heat removal for equipment inside of containment.

The CCW is a closed system utilizing a surge tank with automatic makeup.

During over seven years of commercial operation, no significant CCW leaks have occurred within the containment.

Leakage into the containment would normally be detected using the containment sump level indication; however, this instrumentation is presently inoperable. Accordingly, the District is implementing the following interim measures to ensure leakage into containment will not go-undetected:

(1) The sump pump is operated once per shift.

Pump discharge pressure is monitored and, when the pressure drops substantially, the pump is stopped.

Leakage into the sump will be reflected by increased pumpdown periods.

(2) To detect CCW leakage, the CCW storage tank low level alarm will be set above the automatic makeup level to allow identi-fication of an increased frequency of makeup.

(3) To detect significant leakage of feedwater into the centain-ment, the containment dewpoint will be logged every two hours.

As a long term solution, the inoperable level system will be replaced during the 1981 refueling outage by a dual range containment water level system, as required by NUREG-0737, Item II.F.1(5).

l l

l r

l l

l i

i l

,