ML20003G141

From kanterella
Jump to navigation Jump to search
Submits List of Parameters & Equipment Necessary for Submerged Demineralizer Sys Operation Per Request.Operations Will Be Terminated If All Conditions Are Not Met
ML20003G141
Person / Time
Site: Crane 
Issue date: 04/24/1981
From: Hovey G
METROPOLITAN EDISON CO.
To: Barrett L
Office of Nuclear Reactor Regulation
References
LL2-81-0105, LL2-81-105, NUDOCS 8104280359
Download: ML20003G141 (2)


Text

c> s,.

Metropolitan Edison Cornpany

,- - /ff--

LM f,

Post Of fice Box 480 SJ r "

R Middletown, Pennsylvania 17057

_ _/

k Writer's oirect osal Nurnber April 24, 1981 LL2-81-0105

<\\

fD

\\

\\

'o TMl Program Office Q

[

Attn:

Mr. Lake Barrett, Deputy Director Q

g

(

4 U. S. Nuclear Regulatory Commission

.N i

c/o Three Mile Island Nuclear Station C UI,k.

2 7 7OOI A l-6 l

Middletown, Pennsylvania 17057 O u. s.

\\j sIW'oes h

Dear Sir:

\\

c. '

?

v b

\\\\/

Three Mile Island Nuclear Station, Unit & TL2h i6/

Operating License No. DPR-73 Docket No. 50-320 Submerged Demineralizer System During discussions with your staff, we have been requested to provide an itemized listing of those parameters / equipment necessary for SDS operation. These conditions have been specified to provide additional assurance that SDS processing will be accomplished in a safe manner.

The primary concern addressed here is the potential for gaseous or particulate airborne release through inadvertant release of contaminated water to the fuel handling building atmosphere. The possibility exists that some of the waterborne radionuclides will become airborne. These airborne particulates and gases may be entrained in the plant ventilation system and processed out the plant vent stack. HP-R-219 monitors radio-nuclide effluent from the plant vent stack and is interlocked to stop the ventilation fans and shut the ventilation dampers upon receipt of a high radiation signal (in excess of the instrument setpoint). SDS processing will be terminated if HP-R-219 is inoperable.

During tank farm fill operations, the following conditions have been determined to be important for the health and safety of the public and workers:

1.

HP-R-219 operable.

2.

WG-T-2A, 2B, 2C, 2D tank level indicators operable.

3.

Offgas system ventilation blower in operation.

4.

Filter manifold enclosure vacuum greater than 0.25" WG below ambient pressure.

5.

High Rad filter sample glove box vacuum greater than 0.25" WG below ambient pressure.

During SDS operations, the following conditions have been determined

\\ g3 to be important for the health and safety of the public and workers:

9 iV 810.4280 M i

/

uetrecettan Ee:sen ccmcany is a vemter of the Gereral Puti.c Utet<es System

==

<s Mr. Lake Barrett LL2-81-0105 1.

HP-R-219 operable.

2.

Feed pump manifold enclosure vacuum greater than 0.25" WG below ambient pressure.

3.

Filter manifold enclosure vacuum greater than 0.25" WG below ambient pressure.

4.

Beta manifold enclosure vacuum greater than 0.25" WG below ambient pressure.

5.

Ion exchange manifold enclosure vacuum greater than 0.25" WG below ambient pressure.

6.. Reactor coolant system =anifold vacuum greater than 0.25"-WG below ambient pressure when in use.

7.

Valve IX-24 operable in automatic.

8.

Offgas system ventilation blower in operation.

9.

Offgas bottoms pump operable in either automatic or manual mode.

During SDS process sampling operations, the following conditions have been determined to be important for the health and safety of the public and workers:

~ 1.

HP-R-219 operable.

2.

Sample box in use vacuum greiter ~than 0.25" WG below ambient pressure.

During the course of the SDS operations, should the above specified conditions not be met, we will discontinue the affected operation. That operation will not be resumed without concurrence of the TMI Program Office.

Should you wish to discuss this matter further, please contact Mr. L. J.

Lehman, Jr. of my staf f.

Sincerely, l

/ S /,

.G. K. HOVrf G. K. Hovey Vice-President and Director, TMI-2 GKH:LJL:djb Dr. B. J. Snyder, Program Director - TMI Office cc:

i

,r,

.a

~

., -.