0.,;

}

f

+,fpwtq*,%

UNITED STATES '

f-NUCLEAR REGULATORY COMMISS10N -

n' j

WASHINGTON. D. C. 20555

'+, *....,of March 31, 1981

-Docket No. 50-346 h

U 7

Mr. Richard P. Crouse.

'4 IO81 A Vice President, Nuclear 4$w, d

Toledo Edison Company

),

,. s

\\

Edison Plaza

/

300 Madison Avenue 6

jsg Toledo, Ohio 43652

References:

(~.) NRC letter dated January 7.1980, To.All Power Reactor.

Licensees Concerning Diesel Generator Fuel Oil (2) Toledo Edison Company letter Serial No. 611 dated -

April 18,1930.'

Dear Mr. Crouse:

In Reference (1), we requested that you include diesel generator-(DG) fuel oil within your Quality Assurance Program or provide a justification for not doing so.

In Reference (2) you responded to our request by stating that.DG fuel oil.was not covered within the Davis-Besse Quality Assurance Program, but that measures were in effect at the plant that meet the intent of Regulatory Guide 1.137, " Fuel Oil Systems for Standby Diesel Generators".

You concluded, therefore, that it was not necessary to in-clude DG fuel oil within the Quality Assurance Program.

!!e have reviewed your response and do not consider that you have proposed an acceptable alternative to our position stated in Reference (1).

If you do not intend to include the DG fuel oil within your Quality. Assurance Pro-gram, we consider that your current Technical Specifications regarding DG fuel oil should be revised to include the following requirements:

1.

At least once per 92 days a sample of diesel fuel from each Emergency Diesel Generator Fuel Oil Storage Tanks be obtained-in accordance with ASTM D270-65 and be within the acceptable limits specified in Table 1 of ASTM D975-74 when checked for viscosity, water, and sediment.

2.

Immediately prior to transfer of the diesel fuel oil to an Emergency Diesel Generator Fuel Oil Storage Tank, a sample of fuel being trans-ferred be obtained in accordance with ASTM D270-65 and be within the acceptable limits specified in Table 1 of ASTM 0975-74 when checked ~for-viscosity, water, and seuiment.

810.4100%

f

I i

Mr. F.ichard P. Crouse 'o; are requested to comply with our position of Reference (1)'or, in the al ernative, propose a Technical Specification change to reflect the require-

c.ts stated above. You are requested to reply within 45 days of receipt of

.his letter.

Sincerely,

/

!Jo)kF. Stolz, Chief Operating Reactors Branch !4 U)(vision of Licensing c:

3ee r. ext page i

~,

Toledo Edison Company cc w/ enclosure (s):

N t

Mr. Donald H. Hauser Esq.

U.S. Nuclear Regulatory Commission The Cleveland Electric Resident Inspector's Office Illuminating Company 5503 N. State Route 2 P. O. Box 5000 Oak Harbor, Ohio 43449 Cleveland, Ohio 44101 Director, Criteria and Standards Gerald Charnoff, Esq.

Division Shaw, Pittman, Potts Office of Radiation Programs (ANR-460) and Trowbridge U. S. Environmental Protection Agency 1800 M Street, N.W.

Washington, D. C.

20460 Washington, D. C.

20036

^

Leslie Henry, Esq.

Fuller, Seney, Henry and Hodge U. S. Environmental Protection Agency 300 Madison Avenue Federal Activities Branch Toledo, Ohio 43604 Region V Office ATTN: EIS COORDINATOR Mr. Robert B. Borsum 230 South Dearborn Street Babcock & Wilcox Chicago, Illinois 60604 Nuclear Power Generation Division Suite 420, 7735 Old Georgetown Road Bethesda, Maryland 20014 Ida Rupp Public Library Ohio Department of Health 310 Madison Street ATTN: Director of Health Port Clinton, Ohio 43452 450 East Town Street Columbus, Ohio 43216 President, Board of County Commissioners of Ottawa County Port Clinton, Ohio 43452 Atterney General Department of Attorney General 30 East Broad Street Columbus, Ohio 43215 Harold Kahn, Staff Scientist Power Siting Comission 361 East Broad Street Columbus, Ohio 43216 Mr. Rick Jagger Industrial Commission State of Ohio 2323 West 5th Avenue Columbus, Ohio 43216 Mr. Ted Myers Manager, Nuclear Licensing Toledo Edison Company Edison Plaza 300 Madison Avenue Toledo, Onio 43652