Forwards Hall & Newmark Review of Lll Draft Rept, Seismic Evaluation of Bldg 102 of GE Vallecitos Nuclear Ctr. Recommends That Review Be Adopted as Staff Position
ML20003A097
Person / Time
Site: 07000754
Issue date: 01/19/1981
From: Ayer J, Burkhardt W
NRC OFFICE OF NUCLEAR MATERIAL SAFETY & SAFEGUARDS (NMSS)
To: Rouse L
NRC OFFICE OF NUCLEAR MATERIAL SAFETY & SAFEGUARDS (NMSS)
Shared Package
ML20003A095 List:
References
REF-PROJ-M-3 NUDOCS 8101290529
Download: ML20003A097 (1)


Text

. _ - _ _ _ _

O Distribution:

Docket file JAN I 91981 NMSS R/F FCAF R/F Docket No.70-754

-3 Project File M-3 Project CS urkhardt JEAyer LA File MEMORANDUM FOR: Leland C. Rouse, Chief Advanced Fuel and Spent Fuel Licensigg Branch FROM:

J. E. her Advanced Fuel and Spent Fuel Licensing Branch W. Burkhardt Advanced Fuel and Spent Fuel Licensing Branch

SUBJECT:

SEISMIC EVALUATION OF BUILDING 102 0F THE GENERAL ELECTRIC VALLECITOS NUCLEAR CENTER The purpose of this memorandum is to recomend endorsement of the attached review as a staff position and a basis for succeeding increments of the analysis of the effects of natural phenomena upon existing plutonium fabrication facilities. A draft of the Los Alamos Scientific Laboratory (LASL) report has been reviewed by Dr. C. K. Chou, Lawrence Livemere Laboratory; Dr. J. R. Mcdonald, Texas Tech University; Dr. W. J. Hall and Dr. Nathan H. Newmark, Nathan M. Newmakk Associates; J. Mishima, Battelle Northwest Laboratory; and J. E. %er, W. Burkhardt and Dr. W. E. Vesely, NRC. The final LASL report incorporates the results of that review.

Drs.. Hall and Newmark have documented their assessment in the attached report dated September 29, 1930.

We reconmend that this review including its sur. nary and conclusions be adopted as a staff position subject to your approval.

Subsequent to your approval, we will make copies available to the public and to the General Electric Company in accordance with review and doctnentation procedures agreed upon and described in our February 10, 1977 memorandum to R. M. Bernero.

bisinayste:;g[y

.Jamesz.Ayer J. E. Ayer Advanced Fuel and Spent Fuel Licensing Branch DiyisigjLgg{fgg'lgyand Material Safety

-.W.Burkhardt W. Burkhardt Advanced Fuel and Spent Fuel Licensing Branch Division of Fuel Cycle and Material Safety Original Sisned bg Approved:

Leland C. Rouse 8101290,O h L. C. Rouse, Chief u...___;

r.._,

c___.

e.a

,,___.4 o_.u h.h.

sure:

. CA

.FCA.....

.FCAF.......

O rife o.......... A..s stated.

.J.7 er: fib WBurkgrdt. g EAy LCRouse soR~ -..

..p.

  • T E >..

.L.

.1.1./j.3 /so.

.11/.2//.80..

.11/ti./80.

N R C F O R f.' 314 (9 76; N RC'.* C243 D U.S. GOVERNr.*ENT PRINTING OFFICE: 1979-289 3 69 I

NATHAN M.

NEWMARK '

CONSULTING ENGINEERING SERVICES 1114 CIVIL ENGINEERING BUILDING URBANA. ILLINOIS 61801 29 September 1980 i

r i

Mr. Winston Burkhardt Fuel Reprocessing and Recycle Branch Division of Fuel Cycling and Material Safety US Nuclear Regulatory Commission Washington, DC 20555 Re:

Final Report on Seismic Evaluation of Building 102 at Vallecitos Site Contract NRC-03-78-150

Dear Mr. Burkhardt:

We are enclosing two copies of our final report on the noted facility. The report has been signed by both Dr. Newmark and me.

Sincerely yours, W -) -klf W. J. Hall p9 I

Enclosures (3) cc:

N. M. Newmark 4

M ly /\\

nD 1

Oa e

L 4

s NATHAN M.

NEWMARK CONSUt. TING ENGINEERING SERVICES 1114 CIVIL ENGINEERING BUILDING URBANA, ILLINOIS 61801 29 September 1980 Mr. Winston Burkhardt Fuel Reprocessing and Recycle Branch Division of Fuel Cycling and Material Safety US Nuclear Regulatory Commission Washington, DC 20555 Re: Contract NRC-03-78-150 Seismic Evaluation of Building 102 of the General Electric Vallecitos Nuclear Center

Dear Mr. Burkhardt:

This report contains cur evaluation of the capability of Building 102 of the General Electric Vallecitos Nuclear Center to withstand seismic shaking and fault motion. Our report is based in part on material contained in Ref.1, as well as on the supporting Engineering Decision Analysis Company reports noted in Ref. 1.

One of the authors of this report, Dr. W. J. Hall, visited the site and inspected Building 102 in June 1977 and again briefly in April 1979; in the interim both of us have participated in numerous meetings and telephone conversations with personnel from the U.S. Nuclear Regulatory Commission, with EDAC during l

the early stages, and most recently with LASL concerning evaluation of l

the noted facility.

Description of Facility The General Electric Vallecitos Nuclear Center is located 5 miles SSE of Plea nton, California on the north side of the Vallecitos Valley.

\\V

.. psp y-mo o

1

\\

2 v

)

r NATHAN M.

NEWMARK i

CONSULTfNG ENGINEERING SERVICES 1211 CIVIL ENGINEERING SUILOING URB AN A, ILLtNCIS 618C1 14 April 1980 SEISMIC EVALUATIO 1 0F VALLECITOS SITE by l

fl. M. flewmark & W. J. Hall fiathan M. flewmark Consulting Encineerino Services 1211 Civil Engineering Su11cing Urcana, Illinois 61801 I.

C0:iDITIO:15 CC:1SIDERED At:0 SASIS OF EVALUATI0ti The purpcse of this report is to define a raticnal basis for seismic evaluatien of the General Electric test reactor and other facilities located near Vallecitos, California. The major facilities considered are within three miles of the Calaveras Fault and very close to, or possibly just over, a fault identified as the Verona Fault.

r After discussion with a number of persons and a review of reports, documents, and letters from fiRC, the U.S. Geological Survey, and the TERA Corporation, studies for Diablo Canyon', and recognizing the lack of correlation of damage to structures and equipment in relatica to peak accelera-tien (including the 6 August 1979 Coyote Lake earthquake and the 15 Octobcr 1979 Imperial Valley earthquake), in the light of our judgment and experience we recommend the use of the criteria described herein for the seismic evalua-tion of the site and for the review of structures and equipment in structures at the site.

It is noted that these recommendations are the writers' sole responsibility and do not represent the offici'ai views of f;RC or the USGS.

It is considered that an earth:;uake of magnitude 7 to 7.5 might e

occur on the Calaveras Fault and tha icenter mignt be located close to :he m aH

. _Q

=

L 3

hC9 k W

-w,--

-ww,-

w.

.g,--,-e,,,,,---r,--,-,--,v--

,-,--mmwa e

m

,,w sw--

--,,e

--,e.,-r,,,-

-e, n,

r-v~ e,

notacnmenc c f

i NATHAN M.

NEWMARK I CONSULTING ENGINEERING SERVICES 1211 CIVIL ENGINEERING BUILDING URBANA. ILLINCIS 61801 29 September 1980 SEISMIC EVALUATIO 4 0F VALLECITOS SITE --

BASIS OF EARTHQUAKE GROUtiD MOTION DESIGil CRITERIA by W. J. Hall and fl. M. Newmark fiathan M. tiewmark Consulting Engineering Services 1211 Civil Engineering Building Urbana, Illinoit 61801 IrlTR000CTI0ft The purpose of this background memorandum is to describe in more detail the basis of our reasoning employed in arriving at the recommended seismic review criteria for the Vallecitos site as presented in our memorandum of 14 April 1980. Our reco=endations remain unchanged.

It is important to note that the earthquake ground motion design criteria constitute but one part of the design criteria employed in the design or review of a nuclear facility.

The most important seismic effects for a nuclear plant arising from l

earthquake-induced motions at the site normally would be expected to occur i

from earthquakes having a source close to the site rather than from more l

distant earthquakes on the various fault systems. This observation has been taken into account in arriving at the recommendations for the Vallecitos facility since the sources are considered to be possibly very close to, or under, the site.

Most of the information availfole about earthquake motions is l

probabilistic in nature but, in the absence of definite probabili. ic approaches and established criteria for estimating such effects, the dhl#Tgt 1 JXE

. -.