Ro:On 720525,diesel Generator Failed to Start During Routine Weekly Test.Caused by Low Lube Oil Pressure Trip Due to Low Set & Reset Points on Pressure Switch Ps 673.Settings Adjusted & Diesel Generator Test Operated Successfully
ML20002C730
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 06/23/1972
From: Haueter R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Oleary J
US ATOMIC ENERGY COMMISSION (AEC)
References
NUDOCS 8101100798
Download: ML20002C730 (2)


Text

(,

~R?ru~.1 y ri> cy.

/O' g

CORSumCIS 3 Jug [A//, tgE724-$}!

C0mpany Or i

POWBf

\\..-

.,$g V'

o.a.,.i offic..: 2,2 w..t vienia n A..nu..s.cw.on, uicnia.n 4smoi. Ar.. coo. siv ras-osso

'p'b?/

June 23, 1972 Mr. John F. O' Leary, Director Re: Docket No 50-155 Directorate of Licensing License No DPR-6 US Atomic Energy Co=ission Washington, DC 205k5

Dear Mr. O' Leary:

This is written to apprise you of the failure of the diesel generator to start on May 25, 1972 during a routine weekly test. The diesel generator failed to start because of a " Low Lube Oil Pressure" trip. This occurred on the fourth crank of the first cycle. Four more attempts to start the unit netted the same results. The unit then started on the next or ninth crank.

Subsequent investigation revealed that the set and reset points on pressure switch PS 673 were approximately 3 psi low. The set point was found at 8.2 psig and the reset point at 11.2 psig.

These settings were adjusted to 11.3 psig and 13.3 psig, respectively.

After making the adjustments, the diesel generator was test-operated successfully.

The pressure switch involved is one of two lube oil pressure switches that protect the engine. The operation was such that as the engine cranked at low speed, the switch cocked on the fourth crank (normally a 5 to 7 crank sequence) and due to oil pressure variations at the low crank speed, it=ediately tripped out, interrupting the crank control circuit.

Tests are presently being conducted to determine if the pres-p n,

sure svH.h can be set at a still higher pressure based on the highest pressure observed during cranking. All tripping devices on the unit vill be calibrated and tested on a routine annual basis.

DOCKETED WIC

}

Yours very truly, JUN2 61972 5.~

gk h[

)

y 57 c)

O RBS/sc=

Robert L. Haueter Electric Production CC: BHGrier, AEC-COO Superit.tendent - Nuclear f>, g f/0//O O M 34S8