ML20002C677

From kanterella
Jump to navigation Jump to search
Approves Util 730202 Proposed Change 35 to Tech Specs, Replacing Two Auxiliary antimony-beryllium Neutron Sources in Reactor Core W/Two New Sources.Submits Revised Tech Specs Section 5.1.6
ML20002C677
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 03/02/1973
From: Skovholt D
US ATOMIC ENERGY COMMISSION (AEC)
To: Sewell R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
Shared Package
ML20002C678 List:
References
NUDOCS 8101100705
Download: ML20002C677 (3)


Text

..

4-t z

MAR 2 1973 Docket No. 50-155

'A a-i 3-3-73 Consumers Power Company ATIN:

Mr. Ralph B. Sewell Nuclear Licensing Administrator 212 West Michigan Avenue Jackson, Michigan 49201 Change No. 35 Gentlemen:

License No. DPR-6 Your Proposed Change No. 36 dated February 2,1973, requested changes to the Technical Specifications of Facility License No. DPR-6 to permit replacement of two existing auxiliary antimony-beryllium neutron sources in the reactor core with two new sources. This change is necessary to provide auxiliary neutron sources that are compatible with the nev 11 x 11 rod array fuel bundles that will be used to reload the care in 1974 and theresfter. The old sources cannot fit into the smaller tubes of the Reload G fuel bundles.

Our February 22, 1971 review of the use of the two antimony-beryllium sources presently in.the reactor revealed that the design of the auxiliary neutron sources was conserystive and that saf sty may be enhancod by the insertion and operation with those sources because of the greater ability to measure neutron count rates. The proposed neutron sources are not significantly different from the original sources. Until the activity of the new sources builds up to a use-ful level (1 to 3 years), the origirAl auxiliary neutron sources will remain in core position: close to the startup detectors.

Based on our evaluation, we have concluded that operation of the Big Rock Point reactor with the two new auxiliary neutron sources inserted in its core in the manner proposed does not decrease the ' critical heat l

flux ratius significantly, change the DBA peak clad temperature, increase the probability of or change the consequences of the DBA, nor does it present significant hazards considerationa not described or implicit in the Big Rock Point Safety Analysis Report. There is reasonable assurance that the health and safety of the public will not be endangered by operation in the manner proposed.

7/o//00705 iq w

-w,

k i

Consumers Power Company.# R 2 E73 Accordingly, pursuant to Section 50.59 of 10 CFR Part 50, Section 5.1.e of the Technical Specifications of Facility License No. DPR-6 is hereby changed to read as follows:

"Section 5.1.6 Sources

{i Type Antimony-Beryllium Quantity Two initial Sources and up to Four Auxiliary Sources

  • Location The initial neutron sources shall be placed in core positions 02-59 and 09-52 as shown in Figure 5.1.

Two auxiliary neutron sources may each be contained in a removable rod in a fuel bundle located one fuel bur.dle position from the outside of the core, symmetrically near the east-west line through the center of the reactor core. Two additional auxiliary sources may each be contained in a removable rod in a fuel bundle located in an opposite quadrant from the first two auxiliary sources (i.e., the two additional auxiliary neutron sources will not I

be located in the easternmost 12 fuel bundle quadrant defined by Row 57 and Column 07 or the westernmost 12 fuel bundle quadrant defineu by Row 54 and Column 04).

Physical Description The initial neutron sources shall consist of a steel-jacksted antimony pin,1 inch diameter by 12 inches long, centrally located on the vertical axis of a steel-jacketed (Type 304 SS) beryllium cylinder 5-1/2 OD by 16 inches long. The entire assembly, including support structure, is a cylinder 79-7/16 inches long by 6 inches diameter which rests on a special ori-fice in a standard support-tube-and-channel assembly. A lifting bail shall be provided for handling purposes. The assembly design shall allow adequate cooling along the surface of the source pin and the outer surf ace of the assembly.

)b

r

~

+k Consumers Power Company MAR 2 1973 The auxiliary neutron aources shall each consist of a homogeneous 50-50 mixture of antimony-beryllium first encapsulated in a steel tube (Type 304L SS), then secondarily encapsulated in a zirconium alloy tube. Each doubly encapsulated source will be equipped with a spring-loaded, &ayonet-latch locking device to permit it to be locked into a corner fuel rod position in a fuel bundle.

  • With in-vessel low-level neutron detectors in service, one oper-ating source may be temporarily relocated.s the operator deems appropriate."

Sincerely, originalsigr.ed bg flobert J.Schemd }

Donald J. Skovholt Assistant Director for Operating Reactors Directorate of Licensing cc:

Mr. Paul A. Ferry, Secretary Distribution Consumers Power Company AEC PDR 212 West Michigan Avenue t,R6cket File Jackson, Michigan 49201 RP Reading Branch Reading Mr. Donald W. Aldrich JRBuchanan, ORNL Consumers Power Company IWLaughlin, DTIE Legal Department EPA (3) 212 West Michigan Avenue RBoyd, L: LWR Jackson,..ichigan 49201 DJSkovholt, L:0R TJCarter, L:05 RLTedesco, L:CS ACRS (16)

RO (3)

JScinto, OGC RVollmer, L:QA DLZiemann, L:0RB #2 JJShea, L:0RB #2 RMDiggs, L:0RB #2 NDube, L:0PS MJinks, DRA (4)

SKari, L:RP

..L:0RB #2...

L:0

  1. 2
0. R...............

L:0 B #2 omer >

JJS f.Sdj susmaut >

. -- gs LZi mann ov lt

.!..!.f_h.....

,...f../ 73

.)b]3.,

,3/g,/73 DATE >

Form, AEC-stb (Rev.9-53) ABCM 0240 e u s covt=watNT Pa.Nimma oreca 1972-466 943

~

-.