Forwards Supplemental Response to Violations Noted in IE Insp Rept 50-338/79-47.Corrective Actions:Welder Performance Qualifications Involving Combined Processes Show Separate Thicknesses for Each Process of Combined Process Weld
ML20002B905
Person / Time
Site: North Anna Dominion icon.png
Issue date: 10/14/1980
From: Sylvia B
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20002B906 List:
References
1171C-121979, NUDOCS 8101070294
Download: ML20002B905 (2)


Text

~

(6%

/-

VIRGINIA' ELECTRIC AND Pow en COMPANY Rxcxxxown,VIBGIN KA nun 61

~ 7DcEsber 14, 1980 Mr. James P. O'Reilly, Director Serial No. 1171C/121979 Office of Inspeccion and Enforcement N0/RMT:ms U. S. Nuclear Regulatory Commission Docket No M Region II License No. NPF-4 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

In reference to our letter Serial No. 1171A dated September 17, 1980 regarding the results of a follow-up inspection conducted at North Anna Power Station on September 11 through September 12, 1980, we are forwarding the attached supplemental response.

Very truly yours, B. R. Sylvia anager - Nuclear Operations and Maintenance Enclosure cc:

Mr. Robert A. Clark, Chief Operating Reactors Branch No. 3

(

Division of Licensing l

i 1

?.

b 1' Om gpirY

Enclesure SUPPLEMENTAL RESPONSE TO NOTICE OF VIOLATION IN IE INSPECTION REPORT NO. 50-338/79-47 A.

NRC Comment:

As required by Criterion V of Appendix B to 10 CFR 50 and implemented by Vepco Topical Report VEP-1-A Section 17, paragraph 17.2.5 specifies in part, that activities affecting quality are accomplished in accordance with instructions, procedures, and drawings.

General Welding Procedure W-1.0 Rev. 1 invokes ASME Section IX (74.W76) which under paragraph QW-2013, requires that each welding process or procedure be qualified either separately or in combination with other processes or procedures

...for the deposited weld metal thickness range for each of the processes or procedures... paragraph QW-351 of the same code requires that the limit of thickness of the weld he deposits with each welding process.

Contrary to the above, on November 16, 1979, procedure qualification records of weld process specifications and welder performance qualifi-cations involving combination processes did not indicate the weld metal thickness deposited with each welding process.

This is an infraction.

Response

Pursuant to Section 2.201 of the NRC's " Rules of Practice" Part 2, Title 10, Code of Federal Regulations, the following information is submitted:

1.

Corrective steps taken and results achieved:

The North Anna welder performance qualifications involving combined processes now show separate thicknesses for each process of a com-bined process weld.

2.

Corrective steps which will be taken to avoid further noncompliance:

We believe no further corrective action is required on this item.

3.

DatewhenfullcompliancewillbeaEhieved:

l Full compliance was achieved October 13, 1980.

1 o

T

_