I Pro' nd Changa No. 125 SuphemntNo.6 Telephone 617 366-90ll 710-390-0739 YANKEE ATOMIC ELECTRIC COMPANY m a 's-1<a

~.

?

20 Turnpike Road Westborough, Mossachusetts 01581 m

.Yauxte s.

December 29, 197'S

@/.tiss

\\\\

(

1 p' u United States Nuclear Regulatory Commission

.5 4

)._

Washington, D. C.

20555 p

Attention: Office of Nuclear Reactor Regulation s

4

Subject:

Core XII LOCA Analysis br:3, E

Reference:

(1) License No. DPR-3 (Docket No. 50-29) 3M (2) Proposed Change No. 125, Supplement No. 5, cm.n NC (November 26, 1975).

jp (3) Amendment No. 21 to Facility Operating l3 f

License No. DPR-3, (December 4,1975).

I ' ~. ;

d, id :,.' I3E' 7,

g ~

s-m r-(4)

XN-75-43, " Core Physics Methods and Data Used 1 as Input to LOCA Analysis", Exxon Nuclear 5.1 3..

h Company, (August 1975).

\\q s

gf (5)

Safety Evaluation Report Regarding " Review of Nf y f

the Exxon Nuclear Company PWR Generic ECCS Codes"> C l k Office of Nuclear Reactor Regulation, (September 11, 1975).

Dear Sir:

Pursuant to Section 50.59 of the Commission's Rules and Regulations, Yankee Atomic Electric Company hereby proposes the following modifications to Appendix A to the Technical Specifications.

PROPOSED CHANGE:

It is proposed that paragraph (1) in Section D.2.c. of the referenced Technical Specifications as proposed in Reference (2) and approved in Reference (3) be modified to read as follows in the attached pages.

REASON FOR CHANGE: The limiting LHGR shown in Figure 8-1 originally had a constant flux spike factor included. However, the allowable power level was to be determined using the axially dependent flux spike shown in Figure 8-4.

To eliminate this inconsistency, the flux spike factor has been removed from the limiting LHGR and removed from the calculation of allowable power level. This approach is allowed by Reference (4) which has been approved in Reference (5).

SAFETY CONSIDEFATIONS: Sir.ce the constant flux spike factor included in the original limiting LHGR was greater than that to be used.in the calculation of allowable power level, the power level thus calpulated 8011170 h

t C

, Unitgd St2tre Nucl=r R';gulatory Commission Drc+mber 29, 1975 Attn: Office of Nuclear Reactor Regulation Page Two would have b'een less conservative. This Proposed Change is thus more restrictive and Core XII operation will proceed in accordance with this limit until further change is required.

This Proposed Change has been reviewed by the Nuclear Safety Audit and Review Committee.

SCHEDULE OF CHANGE: Yankee Atomic Electric Company's engineering staff is currently performing analysis of additional breaks and will submit the results by February 2, 1976 as requested in Reference (3).

Any questions regarding this Proposed Change should be directed to Mr. Alan E. Ladieu at our Engineering Office, 20 Turnpike Road, Westboro, Massachusetts, 01581, (617) 366-9011, Extension 2845.

Respectfully submitted, YANKEE A.TOMIC ELECTRIC COMPANY 2.t.\\f D. E. Vandenburgh Vice President COMMONWEALTH OF l'ASSACHUSETTS)

ss.

COUNTY OF UORCESTER

)

Then personally appeared before me, D. E. Vandenburgh, who being duly sworn, did state that he is Vice President of Yankee Atomic Electric Company, that he is duly authorized to execute and file the foregoing request in the name and on the behalf of Yankee Atomic Electric Company; and that the statements therein are true to the best of his knowledge and belief.

l m CW

/

Armand R. Soucy Notary Public My Commission Expires September 9, 1977

,