ML19353B117

From kanterella
Jump to navigation Jump to search

Responds to NRC Re Response to Item 2b of NRC Bullletin 89-001, Failure of Westinghouse Steam Generator Tube Mechanical Plugs. Plugs from Heat 3962 Captured W/ plug-in-plug Type Mod Performed During Refueling Outage
ML19353B117
Person / Time
Site: Beaver Valley
Issue date: 11/29/1989
From: Sieber J
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-89-001, IEB-89-1, TAC-73146, TAC-73147, NUDOCS 8912110226
Download: ML19353B117 (1)


Text

,

4. 'U' t.,

rf ave hey Ftmer State Shwngport. PA 15077&J04 L

i:

n N e aeCauup 1412) 643 W55 s

November 29, 1989 U.

S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC _20555

Reference:

Beaver Valley Power Station, Unit No. I and No. 2 BV-1 Docket No. 50-334, License No. DPR-66 BV-2 Docket No. 50-412, License No. NPF-73 NRC Bulletin 89-01 Gentlemen:

In response to NRC letter dated September 15, 1989 (TAC 73146 and 73147) regarding our response to Item 2b of NRC Bulletin 89-01

" Failure of Westinghouse Steam Generator Tube Mechanical Plugs",

the following supplementary information is provided.

For Beaver Valley _ Unit 1 (BV-1), all of the plugs (6 hot leg and 6

cold' leg) from heat 3962 have been captured with a

" plug-in-plug" type modification performed during the seventh refueling outage.

This completes the required actions for Bullet'in 89-01 for BV-1.

For-Beaver Valley Unit 2 (BV-2) all of-the' hot leg tube plugs modification performed during the _with a

" plug-in-plug" type from heat 3962 were captured first refueling outage.

The remaining BV-2 cold leg tube plugs from heat 3962 will.either be repaired or replaced prior to the tube plug lifetime estimates being exceeded.

The remaining lifetime for these plugs at this time based on the Millstone Unit 2 benchmark is at least 8000 ef fective full' power days _ (EFPD).

If you-have any questions concerning this response, please contact my office.

Very truly yours, 0]r J.

D.

Sieber

/ Vice President

' Nuclear Group cc:

Mr. J.

Beall, Sr. Resident Inspector Mr. W. T.

Russell, NRC Region I Administrator Mr.

P.

Tam, Sr. Project Manager Mr. R.

Saunders (VEPCO) j,7 8912110226 891129

(/

PDR ADOCK 05000334 (d