Forwards LERs 81-009/03L-0,81-010/03L-0 & 81-011/03L-0
Date released: 01/01/2020 Download: ML19352A876


LER 81-011/03L-0:on 810426 & 27,power Operated Relief Valve 445A Declared Inoperable.Caused by Seat Leakage.Valve Stroke Adjusted.Leakage Reoccurred & Valve Isolated.Repair Will Be Accomplished When Plant Conditions Permit
ML19352A883
Person / Time
Site: Farley 
Issue date: 05/26/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19352A883 (1)
LER 81-010/03L-0:on 810429 & 30,containment Atmosphere Radioactivity Monitoring Sys R-11 Declared Inoperable.Caused by Filter Paper Not Advancing Due to Paper Spool Slippage on Shaft.Drive Shaft Adjusted & R-11 Returned to Svc
ML19352A879
Person / Time
Site: Farley 
Issue date: 05/26/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19352A879 (1)
LER 81-009/03L-0:on 810428 & 0501,pressurizer Pressure Indicator PI456 Declared Inoperable.Caused by Out of Spec Indicator Reading Which Occurred During Channel Check. Transmitter Replaced & Channel Returned to Svc
ML19352A877
Person / Time
Site: Farley 
Issue date: 05/26/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19352A877 (2)
Forwards LERs 81-009/03L-0,81-010/03L-0 & 81-011/03L-0
ML19352A875
Person / Time
Site: Farley 
Issue date: 05/26/1981
From: Clayton F
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19352A875 (1)