ML19350D002

From kanterella
Jump to navigation Jump to search
Forwards Request for Addl Info Discussed in 810304,17 & 18 Telcons Re IE Bulletin 80-08, Engineered Safety Feature Reset Controls. Response to Be Submitted within 30 Days of Receipt of Ltr
ML19350D002
Person / Time
Site: Yankee Rowe
Issue date: 03/28/1981
From: Crutchfield D
Office of Nuclear Reactor Regulation
To: Kay J
YANKEE ATOMIC ELECTRIC CO.
References
IEB-80-08, IEB-80-8, LSO5-81-03-066, LSO5-81-3-66, NUDOCS 8104130050
Download: ML19350D002 (3)


Text

filk k

/

'o UNITED STATES NUCLEAR REGULATORY COMMISSION n

l

{

WASHINGTON. D. C. 20555 March 28,1981 Docket No' 50-29 W

LS05-81-03-066 e,

s h o,pp 0 7 Mr. James A. Kay 7gg 3

Senior Engineer-Licensing

'3 sbr / A Yankee Atomic Electric Company cer 1671 Worcester Road g

8 Framingham, Massachusetts 01701 y

,m

Dear Mr. Kay:

On March 13, 1980, the Office of Inspection and Enforcement issued Bulletin 80-08, " Engineered Safety Feature (ESF) Reset Controls."

This Bulletin addresses the concern that the use of reset push buttons alone could permit certain ESF systems components to revert to the normal state following safety system actuation. The Bulletin specified actions to be taken by licensees to address these concerns.

By letter dated June 12, 1980, you responded to the three specific questions asked by the Bulletin.

During our review of your response, we found it necessary to discuss the details of your modifications with members of your staff.

In order that we may complete our safety evaluation on this subject, we request that you submit responses to the attached requests for additional information that we discussed with your representatives in telephone conversations on March 4,17 and 18,1981.

Your response is requested within 30 days of your receipt of this letter.

If you have any questions, please contact us.

Sincerely, 21.Ld' Den is M. Crutchfield, hief Operating Reactors Branch #5 Division of Licensing

Enclosure:

Request for Additional Information cc w/ enclosure:

See next page l

8104180010 G

h Mr. James A. Kay March 28,1981 cc Mr. Janes E. Tribble, President Yankee Atomic Electric Coapany 25 Research Drive Westborough, Massachusetts 01581 Greenfield Community College 1 College Drive Greenfield, Massachusetts 01301 Chairman Board of Selectmen Town of Rowe Rowe, Massachusetts 01367 Energy Facilities Siting Council 14th Floor One Ashburton Place Boston, Massachusetts 02108 Director, Criteria and Standards Division Office of Radiation Prograns (ANR-460)

U. S. Environmental Protection Agency Washington, D. C.

20460 U. S. Environmental Protection Agency Region I Office ATTN: EIS C0ORDINATOR JFK Federal Building Boston, Massachusetts 02203 Resident Inspector Yankee Rowe Nuclear Power Station c/o U.S. NRC Post Office Box 28 Monroe Bridge, Massachusetts 01350 l

l

d REQUEST FOR ADDITIONAL INFORMATION DOCKET NO. 50-29 4

1.

Provide a description and sketch of the containment isolation valve circuit. Snecifically address the following areas:

i 4

a.

Show the redundant solenoid valve circuits on the sketch and describe their operation.

b.

Verify that the bypass switch is an administratively controlled keylock type switch and that annunciation is provided to show that the actuation system is bypassed.

c.

Show the location of the connections for the manual isolation switch in the containment isolation circuit sketch.

2.

Provide a description and sketch of the charging pump control circuit.

3.

Provide a description and sketch of the nitrogen valve solenoid con-trol circuit.

iI

l

.I

n

'