ML19350B306

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 81-06, Failure of Ite Model K-600 Circuit Breaker. No Response Required
ML19350B306
Person / Time
Site: Farley  
Issue date: 03/11/1981
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Mcdonald R
ALABAMA POWER CO.
References
NUDOCS 8103200238
Download: ML19350B306 (1)


Text

_ =..

_ - - - -.~

[

UNITED STATES

[ } ).,,

g NUCLEAR REGULATORY COMMISSION

~\\

  • e REGION 11 9
  • 3*I 101 MARiETTA ST., N.W., SUITE 3100 o

' Q,/

g*

ATLANTA, G EoRGIA 30303 r,".

MAR 111981 S.

u.

3 p

In Reply Refer To:

-in e l' RI -

iTe. i>

U b-

-348

"'.!i s

vi 50-364 s

g g

Alabama Power Company ATTN:

R. P. Mcdonald Vice President-Nuclear Generation P. O. Box 2641 Birmingham, AL 35291 Gentlemen:

)

The enclosed IE Information Notice No. 81-06 contains information that may be applicable to your facility regarding the failure of an ITE Model K-600 cir-cuit breaker.

No specific action or response is requested at this time; however, pending the results of NRC staff evaluations of this matter, further licensee actions may be requested.

Should you have any questions regarding this information notice, please contact this office.

I Sincerely,

/

/

}

James P. O'Reilly Director

~

.n 1.

IE Information Notice No. 81-06 2.

List of Recently Issued IE Information Notices cc w/ encl:

l W. O. Whitt, Executive Vice President F. L. Clayton, Jr., Senior Vice President H. O., Thrash, Manager-Nuclear Generation

0. D. Kingsley, Jr., Manager, Nuclear Engineering and Technical Services-J. W. McGowan, Manager-Operations Quality Assurance i

W. G. Hairston, III, Plant Manager W. C. Petty, Manager-Quality Assurance (Design and Construction)

R. E. Hollands, Jr., QA Supervisor r-l L

8103200 8#

h

.a SSINS No.:

6835 Accession No.:

8011040269 IN 81-06 UNITED STATES

]D 9 i7 NUCLEAR REGULATORY COMMISSION oaj mJ"

{

OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 March 11, 1981 IE Information Notice No. 81-06:

FAILURE OF ITE MODEL K-600 CIRCUIT BREAKER

Purpose:

The purpose of this informaUon notice is to provide early notification of a matter that could adversely affect ths safety of nuclear power plants.

Toward this end this information notice alerts holders of operating licenses and construction permits of a possibly generic deficiency involving Model K-600 circuit breakers manufactured by ITE.

Description of Circumstance:

By letter dated February 20, 1981, the Sacramento Municipal Utility District informed us that, whi_le performing preventive maintenance on electrical circuit breakers at its Rancho Seco facility, an ITE Model K-600 breaker was observed not to trip.

An investigation revealed that a tripping coil wire had slipped i

out of its terminal.

Further examinations revealed that the coil wire size was AWG 20, whereas the mating lug was sized for AWG 16-14 wire.

A check of other ITE electrical breakers indicated that the problem may be generic.

Subsequent to the. letter, the Sacramento Municipal Utility District informed-us orally that ITE Model K-1600 breakers have the same deficiency and that Model K-3000 breakers may be similarly affected.

The information<provided by.the. Sacramento Municipal Utility District is pre.

liminary and will be followed by a complete report.

Consequently, we have not yet evaluated the safety significance of this event.

Nevertheless, the information herein is being provided as an early notification of a possibly significant event. Although no specific action or response is requested at this time, recipients should review the information for possible applicability l

to their facilities.

If NRC evaluations so indicate, further licensee actions nay be requested, i

If you have any questions regarding the information contained herein, please contact the Director of the appropriate NRC Regional Office.

~

Attachment:

Recently issued IE Information Notices e

o

,4 Attachment IN 81-06 March 11, 1981 RECENTLY ISSUED IE INFORMATION NOTICES Information Date of Notice No.

Subject Issue Issued to 81-05 Degraded DC System at 2/10/81 All power reactor Palisades facilities with an OL or CP 81-04 Cracking in Main Steam 2/27/81 All power reactor Lines facilities with an OL 81-03 Checklist for Licensees 2/12/81 All power reactor Making Notifications of facilities with an Significant Events in OL Accordance with 10 CFR 50.72 81-02 Transportation of 1/23/81 All Radiography Radiography Devices licensees 81-01 Possible Failures of 1/16/81 All power reactor General Electric Type facilities with an HFA Relays OL or CP.

80-45 Potential Failure of 12/17/80 All PWR facilities BWR Backup Manual Scram with an OL or CP Capability Actuation of ECCS in the 12/16/80 All PWR facilities

'80-44 Recirculation Mode While with an OL or CP l

in Hot Shutdown 80-43 Failures of the Continuous 12/5/80 ~

All power reactor Water Level Monitor for facilities with an the Scram Discharge Volume OL or CP at Dresden Unit No. 2 i

80-42 Effect of Radiation on 11/24/80 All power reactor l

Hydraulic Snubber Fluid facilities with an l

OL or CP l

80-41 Failure of Swing Check 11/10/80 All power reactor l

Valve in the Decay Heat facilities with an Removal' System at Davis-OL or CP j

Besse Unit No. 1 l

OL = Operating Licenses CP = Construction Permits l

l i