ML19347F459

From kanterella
Jump to navigation Jump to search
Forwards LER 81-052/03L-0
Date released: 12/27/2019 Download: ML19347F459


LER 81-052/03L-0:on 810415,RHR Pump 1B Tripped.Caused by Improperly Installed Cover on Pump Torus Section Valve Motor Operator Allowing Corrosion Buildup on Electrical Contacts of Start/Run Limit Switch.Contacts Cleaned.Cover Adjusted
ML19347F460
Person / Time
Site: Brunswick 
Issue date: 05/12/1981
From: Pastva M
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19347F460 (2)
Forwards LER 81-052/03L-0
ML19347F458
Person / Time
Site: Brunswick 
Issue date: 05/12/1981
From: Dietz C
CAROLINA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19347F458 (1)