ML19347E377

From kanterella
Jump to navigation Jump to search
Safety Evaluation Re Susceptability of safety-related Sys to Flooding from Failure of Non-Category 1 Sys.Licensee Analysis Is Acceptable.Recommends Licensee Analysis Re Turbine Bldg Flooding Due to Circulating Water Pipe Failure
ML19347E377
Person / Time
Site: Maine Yankee
Issue date: 04/13/1981
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML19347E375 List:
References
NUDOCS 8104270178
Download: ML19347E377 (2)


Text

'

ENCLOSURE OV SAFETY EVALUATION REPORT SUSCEPTIBILITY OF SAFETY-RELATED SYSTEMS TO FLOODING FROM FAILURE OF NON-CATEGORY 1 SYSTEMS FOR MAINE YANKEE ATOMIC POWER STATION I.

INTRODUCTION By letter to the Maine Yankee Atomic Power Company (MYAPCO) dated September 27, 1972, we requested MYAPC0 to review the Maine Yankee Atomic Power Station to determine whether the failure of any non-Class 1 (seismic) equipment could result in a condition such as flooding that might adversely affect the safe shutdown of the facility.

By letter to us dated October 20,1972, MYAPC0 responded to the original NRC request, furnishing information on postulated failure of the service water pumps and the circulating water pumps.

On June 7,1973, MYAPC0 submitted additional detailed information to us a

which was the result of an extensive study conducted on the effects of piping failure external to the Containment Building. Proposed modifi-cations to the system as outlined in this letter were not acceptable to us.

Revised modification designs were outlined by MYAPC0 in their letter to us dated October 19, 1973.

I We transmitted to MYAPC0 on December 17, 1974, a set of Guidelines for Protection from Flooding of Equipment Important to Safety. These guide-l lines expanded on the scope of MYAPCO's original study and required I

further study of the flooding problem by MYAPCO.

MYAPCO responded ~ to our Guidelines by letter reports dated January 23, l

1975 and February 19, 1975.

l The various sources of potential flooding identified by MYAPC0 and the affected safety-related equipment are discussed in the enclosed consultant's report.

II.

EVALUATION The enclosed technical evaluation report was prepared for us by our consultant, the Lawrence Livermore National Laboratory, as part of the Selected Operating Reactors Issues Program, FIN A0250.

t 8104 270 l~f f

III. CONCLUSIONS The consultant has reviewed the licensee's submittals for Maine Yankee to determine if postulated failures of non-Category 1 (seismic) components could adversely affect the operabflity of safety-related equipment.

We conclude that the licensee has demonstrated in their analysis that the Maine Yankee Atomic Power Station, excluding the Turbine Building, has the capacity arid capability to manage and mitigate any single incident, such as flooding from a non-Class 1 system component or pipe, so that flooding will not prevent the safe shutdown of the plant and, is therefore, acceptable.

The licensee has further shown in the analysis for those areas addressed, that no single failure would result in common mode failure of redundant safety-related equipment.

We recommend that the licensee be required to submit an analysis of flooding of safety-related equipment in the Turbine Building resulting from failure of the circulating water piping or expansion joint in this area. The receipt of this analysis is required to enable us to complete the evaluation for flooding of safety-related equipment / systems at the Maine Yankee Atomic Power Station.

I

1 SELECTED ISSUES PROGRAM TECHNICAL EVALUATION OF THE SUSCEPTIBILITY OF SAFETY-RELATED SYSTEMS TO FLOOGING CAUSED BY THE FAILURE OF NON-CATEGORY I SYSTEMS FOR THE MAINE YANKEE ATOMIC POWER STATION Docket No. 50-309 by Richarc C. Epps February 1981 Nuclear Systems Safety Program Lawrence Livermore National Laboratory C; R.. 5. 75"""7'T@.'m.1, c,,a< :ymmm*-e:7'; Califcrnia c

gg

-~

=

w.

hf DUPLICATE DOCUMENT klS Entire document previously entered into system under:

8/03//o 84'o i

ANo

~

No. of pages:

//,3 is % 2" m :;; w z = ?, xu:.: ~ a m e;; _=

!)

'