Responds to 800730 Final Rept Re Deficiencies in Rock Anchor Design & Shear Wall Design.Rept Does Not Provide Sufficient Detail to Enable NRC to Determine Sufficiency of Corrective Actions
ML19347C865
Person / Time
Site: Millstone Dominion icon.png
Issue date: 01/29/1981
From: Robert Carlson
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Counsil W
NORTHEAST NUCLEAR ENERGY CO.
References
NUDOCS 8103100158
Download: ML19347C865 (1)


Text

g"%

-f s 4

Io,,

UNITED STATES NUCLEAR REGULATORY COMMISSION y j ) s.,

g ti *

.j REGION 1 0

4 631 PARK AVENUE

"$, +.V

,o#

KING OF PRUSSIA, PENNSYLVANIA 19406 Docket No. 50-423 2 9 JAE '937 Northeast Nuclear Energy Company 6

ATTN: Mr. W. G. Counsil B

Senior Vice President - Nuclear Engineering and Operations g,,pgg2s788/g

(

M' P.O. Box 270 Hartford, Connecticut 06101 g

g s

/

z y 4+ V Gentlemen:

y'a

Subject:

Deficiencies in Rock Anchor Design and Shear Wal esign (Reference your letter dated July 30, 1980 and our letter datedSeptember3.1980)

We have reviewed your letter of July 30, 1980 pertaining to the 10 CFR 50.55(e) reportable item of deficiency in rock anchor design. Your report does not provide sufficient detail, as required by 10 CFR 50.55(e), to enable the staff to make a detennination of the sufficiency of corrective action taken. Please

. provide us with the detailed analysis of the safety implications and corrective action taken in relation to the rock anchor design.

In addition, it is our determination that a separate and distinct problem has been identified in relation to the incorrect shear wall design calculations.

l You should report this as a separate problem in accordance with the provisions of 10 CFR 50.55(e).

t

(

l Your cooperation with us is appreciated.

Sincerely, f

5{

Robert T. Carlson, Chief Reactor Construction and Engineering Support Branch cc:

K. W. Gray, Supervisor of Construction Quality Assurance H. R. Nims, Director of Nuclear Projects E. J. Mroczka, Station Superintendent J. R. Himmelwright, Licensing Safeguards Engineer D. G. Diedrick, Manager of Quality Assurance i

l M

l 8108100 b

t

' MUlil'aiint!71' tri'II.!Tilib

.f.

f.[hhk'$.$

1 i

?

mc:>cm mi e

w

= = = =

July 30, 1980 Docket'No. 50-423 AEC-MP3-213 B10044 Mr. B. H. Grier, Director United States Nuclear Regulatory Commission Region I o31 Park Avenue

~

King of Prussia, Pennsylvania 19406 Gentlemen:

Millstone Unit No. 3 Reporting of Deficiencies in Desian and Construction This letter provides final reporting as coamitted by NNECO in its

' y,T,,3

)(g) previous letter of JQcf3,1980, on the structural problems encountered in the Service, Auxiliary, and Turbine Buildings at Millstone Unit hy/

No. 3.

As previously reported, the Service Building was reportable under 10CFR50.55(e)(1)(ii),and has been corr,ected.

Further analysis has shown that the Turbine Building problem is not safety related, and therefore not reportable.

-The review of the Auxiliary Building structural analysis has concluded that;it is reportable under 10CFR50.55(e)(1)(ii).

The remainder of this

. report will deal with the details of the Auxiliary Building problem and corrective changes instituted by Stone & Webster Engineering Corporation.

The review of the Auxiliary Building design determined that horizontal seismic loads were distributed to shear walls according to their relative stiffness at each floor.

However, the ' analysis was incomplete in that

-the moments and vertical forces at each level of the building resulting

.from horizontal seismic forces were not carried down through the structure

-in a consistent. manner.

.bupc v4692 3 933)6

~

i To resolve the problem, an independent seismic review of the Auxiliary Building was performed.

A response spectrum modal analysis using a three-dimensional lumped mass model was employed.

Three orthogonal directions of excitation were used (two horizontal and one vertical),

with vertical excitation taken as two-thirds of the horizonal excita-tion.

The seismic responses were used in conjunction with the detailed structural model to determine the seismic stress resultants in the structural walls in the building.

The primary structural elements of the building were reviewed on this basis, and it was determined that certain modifications are required to resist seismic loads.

These modifications include increasing the reinforcing in certain walls and slabs, installing rock anchors' on the building perimeter and providing additional interior columns and walls.

The structural changes required in the Service Building and Auxiliary Building are a result of the incompleteness of the calculational methods and mcdels employed originally.

These methods and models were selected by the individual who performed the building calculations and were indepsndently checked by a similarly qualified individual not previously involved with the work.

In this situation, the preparers and checkers who were associated-with the Millstone 3 project, produced a consistent project calculational' method, but did not detect the incomple'.e aspect of the method.

In order to preclude the recurrence of the use of a similar inappropriate analytical method, Stone & Webster has reinforced its Structural Technical Review program.

This corporate program, under the direction of an Assistant Chief Structural Engineer includes a review and approval of all design criteria to be used in the design of structures as well as the analytical approach and methods to be used.

The program also includes the scheduling of a series of reviews during the' design process to assure proper application of the criteria and methods and to detennine the acceptability of the final design.

This program is staffed with senior engineers and consultants with extensive experience in the areas of dynamic analysis, design, and engineering of various types of structures.

In addition to the scheduled involvement of these individuals, they are available to the project groups whenever their particular expertise might be required.

The implementation of this program will assure a proper and uniform design.

~

.. d i

m-

_3

\\

4 We trust that this report addresses any remaining concerns you may have on.this subject.

Very truly yours, NORTHEAST NUCLEAR ENERGY COMPANY J V/ld i

W. G. Counsil Senior Vice President