Approves Proposed Change 23 to Tech Specs,Modifying Reactor Nuclear Instrumentation Sys to Add Three Power Range Panels, Three Linear Power Meters & Auxiliary Panel Per 620509 Request
ML19347C489
Person / Time
Site: Yankee Rowe
Issue date: 08/23/1962
From: Lowenstein R
US ATOMIC ENERGY COMMISSION (AEC)
To: Coe R
YANKEE ATOMIC ELECTRIC CO.
Shared Package
ML19347C490 List:
References
NUDOCS 8011190754
Download: ML19347C489 (2)


Text

NhyP(,

~-

(_

UNITED STATES f

f T

ATOMIC ENERGY COMMISSION i

  • II/*

WASHINGTON 25. D.C.

fh{

%n e 23 m Docket No. 50-29 Change No. 23

_ i'.

i i

Yankee Atomic Electric Company h[

441 Stuart Street

(.I.U$ [

s Boston 16, Massachusetts E-Attention:

Mr. Roger J. Coe Vice President y;

Gentlemen:

This refers to your request, dated May 9,1962, for AEC authorization to make Proposed Change No. 23 in your facility pursuant to paragraph W

3.A. of License No. DPR-3, as amended.

We have reviewed the proposed' change in technical specifications and ME have found that certain modifications in your reactor nuclear instru-Ij) mentation system consisting of the addition of three power range h

panels, three linear power meters and an auxiliary panel as proposed p

and as modified below do not present significant hazards considerations not described or implicit in the license application as amended to June 23, 1961, and that there is reasonable assurance that the health and safety of the public will not be endangered by.,peration of the facility as proposed and as modified below.

It is our opinion that change should be made in the technical specifications to require four (4) rather than the two (2) _ operable channels presently required for reactor operations, as listed in the techni' cal specifications under Table' I, High Neutron Flux Level-Reactor Scram.

In addition, the requirements of Precaution III.5. of Operating Instruction 5040 should be changed to read as follows in order to define the limi-tations involved in the coincidence requirements more explicitly:

III.5 The following minimum operating instrument requirements must be met:

Four detectors monitoring power whicli ;;rovide automatic a.

high level scram protection.

b.

(1)

In a condition where one upper or one lower power range channel is inoperative, the reactor can continue to be operated at the existing power level provided no major rod program change is 8011190 75'/

p y

(

(.

5

_ AUG 2 31961 carried out and provided the power range high level scram protection is set for single channel operation for the group containing the failed channel.

m.

(2) In a condition where two power range channels are inoperative, the reactor can continue to be operated

. =:.

at the existing power level provided no major rod program change is carried out and provided the power range high level scram protection is set for single channel operation on both the upper and lover group.

h~

6..:.

.=.::

In view of the foregoing, Yankee Atomic Electric Company is hereby authorized under License No. IPR-3 to make certain modifications in their reactor nuclear instrumentation system consisting of the addition of three power range panels, three linear power meters and an auxiliary

=<:,

panel in accordance with Yankee's request dated May 9,1962, entitled

-==

proposed Change No. 23 as modified above.

r ::=:

Sincerely yours, g i..{

(::==1.,

d cri @ d S W by R. tcwenstein.

.7 Director Division of Licensing and Regulation

Enclosure:

Hazards Analysis Distri ation 7=

C. K. Beck E. Tremac1 R. Lowenstein H. Steele

~

E. G. Case R. Huard H. Shapar R. Cunningham P. Travelstead Doc. Room R

l P. A. Morris Formal E. E. Hall Suppl.

R l

D. C. Clark LB-L6R readings DESR DLSR 16 OGC DLGR Y

% 6) g l

D rec *or NOUason/dk !!Gaske ru t

8/13/62 h

b IN

..],[

l i

l

~

.nc-

--g---

-,,n n

m-