ML19346A418

From kanterella
Jump to navigation Jump to search
Forwards LERs 81-023/03L-0,81-024/03L-0,81-026/03L-0, 81-027/03L-0,81-031/03L-0,81-032/03L-0 & 81-036/03L-0
Date released: 12/26/2019 Download: ML19346A418


LER 81-036/03L-0:on 810526,diesel Generator 1-2A Failed to Reach Rated Speed & Voltage within Time Required.Cause Unknown
ML19346A427
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A427 (1)
LER 81-032/03L-0:on 810508,diesel Generator 1C Failed to Start During Operability Test.Caused by Leaking Seal Between Inner & Outer Cylinder Which Allowed Water to Fill Cylinder 10.Cylinder Liner Replaced
ML19346A426
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A426 (1)
LER 81-031/03L-0:on 810506,day Tank Fuel Level on Diesel Generator 1B Found Low.Caused by Operator Error.Tank Filled. Operators Reinstructed to Closely Monitor Tank Level.Design Change Being Evaluated
ML19346A425
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A425 (2)
LER 81-027/03L-0:on 810429 & 30,injector Fuel Oil Leak Found on Diesel Generator 1-2A.Caused by Leaking Injector Seals. Seals Replaced
ML19346A424
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A424 (1)
LER 81-026/03L-0:on 810506,on Two Separate Occasions,Diesel Generator 1C Failed to Reach Rated Speed & Voltage within Required Time.Caused by Faulty Fuel Oil Check Valve.Valve Replaced
ML19346A423
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A423 (2)
LER 81-024/03L-0:on 810501,high Differential Pressure Across Strainer Found on Diesel Generator 1-2A.Caused by Excessive Accumulation of Lube Oil Sediment/Dirt in Strainer.Strainer Cleaned
ML19346A422
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A422 (2)
LER 81-023/03L-0:on 810425,fuel Oil Found Leaking on Diesel Generator 1-2A.Caused by Failed Fuel Oil Filter Gasket. Gasket Replaced
ML19346A420
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A420 (1)
Forwards LERs 81-023/03L-0,81-024/03L-0,81-026/03L-0, 81-027/03L-0,81-031/03L-0,81-032/03L-0 & 81-036/03L-0
ML19346A417
Person / Time
Site: Farley 
Issue date: 06/12/1981
From: Clayton F
ALABAMA POWER CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19346A417 (1)