ML19345G215

From kanterella
Jump to navigation Jump to search
Forwards Revised IE Bulletin 81-01, Surveillance of Mechanical Snubbers, W/Corrected Pages 5 & 6.Util Is Added to CP Facilities to Which Bulletin Is Applicable.Response Should Include Estimate of Manpower Expended
ML19345G215
Person / Time
Site: Grand Gulf 
Issue date: 03/04/1981
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Stampley N
MISSISSIPPI POWER & LIGHT CO.
References
NUDOCS 8103170098
Download: ML19345G215 (1)


Text

P

% [ p;r4 9'o UNITED STATES c

8 'j* ) ~.,, f[*s NUCLEAR REGULATORY COMMISSION g

.\\ '

p-c REGION 11 k

101 MARIETTA ST., N.W.. SulTE 3100 g*v,/

ATLANTA. GEORGIA 30303 MAR 1 1981 fv,)$!Ja,'/

,/

t In Reply Refer To:

//

9, RII:JP0

(~g I(/bY ar OO 1

Mississippi Power and Light Company

' t 4 klg*eg/Sg7A -

ATTN:

N. L. Stampley

~

s %..y Vice President of Production g

P. O. Box 1640

[

Jackson, MS 39205 v

e gg Gentlemen:

IE Bulletin 81-01 has been revised to add your power reactor facility to those with construction permits to which the bulletin is applicable. As a result, the enclosed IE Bulletin No. 81-01, with revised pages 5 and 6, is forwarded for your action with regard to your power reactor facility.

To assist NRC in evaluating the value/ impact of each bulletin on all licensees, it would be helpful if you would provide an estimate of the manpower expended in the review and preparation of the report (s) required by the bulletin.

Please estimate separately the manpower associated with corrective actions required by this bulletin.

Should you have any questions regarding this bulletin, its revision, or the actions required of you, please contact this office.

Sincerely, K9 James P. O'Reilly Director

Enclosure:

1.

IE Bulletin No. 81-01 with revised pages 5 and 6 2.

List of Recently Issued Bulletins cc w/ enc 1:

C. K. McCoy, Plant Manager

SSZNS No.:

6820 Accession No.:

8005050075 IEB 81-01 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 January 27, 1981 IE Bulletin No. 81-01: SURVEILLANCE OF MECHANICAL SNUEBERS Description of Circumstances:

Several instances of failures of mechanical snubbers supplied by International Nuclear Safeguards Corporation (INC) have been identified that indicate possible deficiencies in these snubbers. A summary of the failures that have occurred is provided below:

1.

On August 9, 1974, the Tennessee Valley Authority submitted event report BFAO-50-260/741W identifying 11 of 14 INC Model MSVA-1A snubbers that were found inoperable on Browns Ferry Nuclear Power Station Unit 2 and subsequently identified 5 of 14 inoperable units on Browns Ferry Nuclear Power Unit No 3.

All of these units were found to be frozen, and the cause was attributed to a failure to lubricate the parts during assembly.

The failed snubbers were replaced with new units produced by the same manufacturer.

2.

On April 12, 1976, the St. Lucie Plant Unit 1 facility of Florida Power and Light Corporation submitted event report No. 50-335-76-9 wherein five INC Model MSVA-1 snubbers were identified as inoperable because they were found to be frozen.

The failures were caused by oxidation on the internals and by iinproper assembly.

All.INC. mechanical snubbers were replaced with units produced by ano'ther ma'nufacturer.

3.

On April 8, 1977, Iowa Electric Light and Power Company submitted event i

report No. 77-23 for the Duane Arnold Energy Center facility that identi-l fied 13 INC Model IMSVA-1 Type AS snubbers to be frozen; the cause of failure was attributed to large amounts of interior oxidation.

The units were replaced with those produced by another manufacturer.

4.

On December 5, 1979, personnel from the Nuclear Regulatory Commission visited Department of Energy (DOE) facilities at Richland, Washington, to obtain information on DOE experience with INC snubbers at the Fast Flux Test Facility (FFTF).

The DOE-owned FFTF was equipped with more than 4,000 mechanical pipe restraints (srubbers) supplied by INC.

In 1978, FFTF examined more than 800 NT l