ML19345G069

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 81-01, Possible Failures of GE Type Hfa Relays. No Response Required
ML19345G069
Person / Time
Site: Marble Hill
Issue date: 01/16/1981
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Shields S
PSI ENERGY, INC. A/K/A PUBLIC SERVICE CO. OF INDIANA
References
NUDOCS 8102190883
Download: ML19345G069 (1)


Text

.

ret 2A

'o UNITED STATES E'

NUCLEAR REGULATORY COMMISSION 3

o

.E REGION 111 0,

[

799 ROOSEVELT ROAD g"

GLFN ELLYN, ILLINOIS 60137 January 16, 1981 Gentlemen:

This Information Notice No. 81-01 is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding this matter, please contact this office.

Sincerely, a.B w

e< James G. Keppler i

Director i

Enclosure:

IE Information Notice No. 80-01 l

81021.90%93 i

's Docket No. 50-546 Docket No. 50-547 Public Service of Indiana ATTN: tir. S. W. Shields Senior Vice President Nuclear Division Post Office Box 190 New Washington, IN 47162 cc w/ encl:

Steve J. Brewer, Nuclear Safety and Licensing Supervisor M tral Files AD/ Licensing AD/ Operating Reactors PDR Local PDR NSIC TIC LeBoeuf, Lamb, Leiby & !!acRae Dave ?!artin, Office of the Attorney General John R. Galloway, Staff Director, Environment, Energy and Natural Resources Subcommittee C.

T c0' Y

y 8,% -[g 6 h,fa UL97

~.

Ik

SSINS No.:

6835 Accession No.:

8011040254 IN 81-01 UNITED STATES NUCLEAR REGULATORY COMMISSION m'n OFFICE OF INSPECTION AND ENFORCEMENT OlrN P

j WASHINGTON, D. C.

20555 M

MJ ly January 16, 1981 IE INFORMATION NOTICE NO. 81-01: POSSIBLE FAILURES OF GENERAL ELECTRIC TYPE HFA RELAYS

Purpose:

The intent of this Information Notice is to alert licensees and holders of construction permits of a potentially generic problem involving defective coil spools used in General Electric (GE) type HFA relays.

Such defective relays were recently found at Turkey Point Unit 4 (Docket No. 50-250).

Description of Circumstances:

The defective coil spools are fabricated of either black or clear Lexan, a polycarbonate material that is susceptible to surface cracking when exposed to hydrocarbons.

The concern here is that such surface cracks could ultimately j

deteriorate to such a degree that relay actuation would be blocked by the resultant debris, thereby inhibiting a required safety function.

Indications of the above mentioned cracks were recently detected on the HFA relays used to sequence the emergency loads on the diesel generators at Turkey Point Unit 4 upon a loss-of-coolant accident coincident with a loss of offsite power. A'ter detecting the cracks, the spare coils in the storeroom were in-spected and, although these coils are new units, one was found to be cracked.

The possible failures of GE type HFA relays highlights two salient points:

(1) HFA relays have had a long history of failures (e.g., GE has issued several Service Information Letters (SIL) addressing these relays, the oldest.one of l

which dates back to 1973, and it is anticipated that GE will issue a new SIL in the near future addressing this new concern); (2) the cracking phenomena seems to be similar to that experienced on the cam followers used on GE type SBM switches (e.g., these cam followers are fabricated of Lexan, and after l

their exposure to hydrocarbons during fabrication or during maintenance severe cracking resulted.

See IE Information Notice No. 80-13 for additional details.)

The at' ve information identifies means whereby the integrity of a major safety celated system can be jeopardized or compromised by the blocking of relay actuation. Accordingly, this Information Notice ', provided as an early r.otification of a possibly significant matter that is still under review by the NRC staff.

Recipients should, therefore, review the information for possible applicability to their facilities.

Although no specific action or response is requested at this time, further licensee actions may be requested or required pending the outcome of.the NRC staff evaluation.

If you have any question regarding-this matter, please contact the director of the appropriate NRC Regional Office.

4 S

IN 81-01 January 16, 1981 RECENTLY ISSUED o

IE INFORMATION NOTICES Information Date of Notice No.

Subject Issue Issued to 80-45 Potential Failure of 12/17/80 All PWR facilities BWR Backup Manual Scram with an OL or CP Capability 80-44 Actuation of ECCS in the 12/16/80 All PWR facilities Recirculation Mode While with an OL or CP in Hot Shutdown 80-43 Failures of the Continuous 12/5/80 All power reactor Water Level Monitor for facilities with OL the Scram Discharge Volume or CP at Dresden Unit No. 2 80-42 Effect of Radiation on 11/24/80 All power reactor Hydraulic Snubber Fluid facilities with OL or CP 80-41 Failure of Swing Check 11/10/80 All power reactor Valve in the Decay Heat facilities with an 0:

Removal System at Davis-or CP Besse Unit No. 1 80-40 Excessive Nitrogen Supply 11/10/80 All power reactor Pressure Actuates Safety-facilities with Relief Valve Operation to OL or CP Cause Reactor Depressur-ization 80-39 Malfunctions of Solenoid 10/31/80 All light water reactor i

Valves Manufactured By facilities with l

Valcor~ Engineering Corporation OLs or cps l

80-38 Cracking in Charging Pump 10/30/80 All PWR facilities l-Casing Cladding with an OL or CP 80-37 Containment Cooler Leaks 10/24/80 All power reactor and Reactor Cavity facilities with l

Flooding at Indian Point OLs or cps l

Unit 2 OL = Operating Licenses CP = Construction Permits