Suppls 801105 Response to IE Bulletin 80-11 Re Masonry Wall Design Deficiencies.All Multiple Wythe Walls Will Behave as Composite Walls (Item 2b(iii)a)
ML19345E053
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 11/25/1980
From: Furr B
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-80-11, NO-80-1746, NUDOCS 8012230018
Download: ML19345E053 (4)


Text

/

-}

9 ct 1.

C3 i

November 25, 1980 i

1

,a FILE:

NG-3513 (B)

SERIAL:

NO-80-1746 M

na vs a

?!r. James P. O'Reilly U.S. Nuc3 3ar Regulatory Commission Region II 101 ?!arietta Street, Suite 3100 Atlanta, GA 33303 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 LICENSE NOS. DPR-71 AND_DPR-62 DOCKET NO

__a -325 AND 50-324

~

SUPPLEMENTAL RESP NSP TO TF ITUttefwE6-11

Dear Mr. O'Reilly:

Enclosed you will find Carolina Power & Light Company's supplemental response to IE Bulletin 80-11 concerning Masonry Wall Design.

This response addresses additional information required by Item 2b(iii)(a),

concerning the Brunswick Unit Nos. I and 2 Reactc r Buildings, and Item 2b(iii)(b).

As stated in our November 5, 1980, response, the information for the Diesel Generator Building will be provided by December 9, 1980.

Should you have questions regarding our response, please contact my staff.

Yours very trulv, I J. Fur-Vice President Nuclear Operations DCS:ejj*

Enclosure cc:

Mr. Norman C. Moseley Sworn to and subscribed before me this the 4 5 ^ day of w ev&vx.be4 1980.

Yh

~

V Notary Pub'lic My Commission Expires h6 19 3 U

OFFICIAleCUI

m Item 20(iii)(a)

Report ror fu. ctor Buildings - Unit I and Unit 2 The on-site survey revealed the following:

(1) Wall 2A, Unit I has a 5'-0" x 6'~1" opening in the wall that is not shown on the drawings.

The opening is filled with solid concrete masonry blocks that are stacked full depth but not mortared.

This wall will be modified.

All safety-related masonry walls were reevaluated using floor response spectra curves specially developed for this report.

The calculations followed the Acceptance Criteria (Appendix 80-11-A from our November 5, 1980, response) and embraced both OBE and DBE seismic input.

Interface tension between wythes resulting from an attached load is less than 0.5 psi.

The results of the calculations were recorded as a stress factor; i.e.,

as a ratio of actual stress to allowable stress.

A range of stress factors is given on Attachment A.

Conclusions-Following modification of the wall indicated above:

All multiple wythe walls will behave as composite walls.

All safety-related concrete masonry walls in the two Reactor Buildings have structural integrity.

I a

Item 2b (iiil (b)

The safety-related concrete masonry walls at Carolina Power & Light Company's Brunswick Plant having multiple wythe construction are all in the Reactor Buildings. The multiple wythe walls serve as shield walls (see Table 80-11-3 from our November 5, 1980,. response).

No safety-related equipment is attached to these walls except for light items such as an electrical panel, a junction box, or lighting fixture.

Multiple wythe walls were designed as composite and the shear stress in the. interface between the wythes was checked.

See Report for Reactor Buildings under Item 2b (iii) (a) for stress factors for the multiple wythe walls.

f ATTACIIMENT A Reactor Building - Lnit #1 Pult iple Wyt he Walls

-0BE DBE i

Masonry - Coapression 0.02 to 0.11 0.01 to 0.07 Maseur Tension 0.12 to 1.0 0.12 to 0.95 i

Mortar - Shear 0.02 to 0.10 0.02 to 0.10 i

Mortar - Collar Joint Shear 0.14 to 0.86 0.15-to 0.92 c

S iiipl e Wv t_b e Wa 1,1 s "a8onry - Compression 0.02 to 0.10 0.01 to 0.06 Masonrv - Tension 0.15 to 0.54 0.11 to 0.51 l

Mortar - Shear 0.04 to 0.15 0.04 to 0.17 4

i

@!1d ]!0dFC'i 1

Reinforcing - Tension 0.15 0.11 t

l Reinforcinn - Bond 0.18 0.22 i

i I,

1 l

Reactor Building - l' nit // 2 Mult_if e Wvthe Wa11 I

Masonry - Compression 0.02 to 0.11 0.01 to 0.07 Masonry - Tension 0.02 to 1.0

'O.12 to 0.95 Mortar - Shear 0.02 to 0.04 0.02 to 0.04 Mortar - Collar Joint Shear 0.14 to 0.28 0.15 to 0.31 S_ ingle Wythe Walls Masonry.- Compression 0.02 to 0.10 0.01.to 0.06 Masonry - Tension 0.15 to 0.54 0.11 to 0.51-Morta r - Shear 0.04.'to 0.15 0.04 to'O.17 l

nond Beams f

0.15 0.11

.Reipforcing - Tension.

Reinforcing - Cond :

0'.18 0.22 i

I