Forwards LER 80-050/03L-0
Date released: 12/25/2019 Download: ML19345D833


LER 80-050/03L-0:on 801115,breaker for Standby Liquid Control Pump B Motor Tripped When Pump Started.Caused by Overcurrent Tripping Device on B Phase Tripping at Lower Value than Other Phases.Breaker Replaced