. _. _

m.

TENNESSEE VALLEY AUTHCR!TY csATTANeoaA r newsazz m :;t 3

400 Chestnut Street Tower II November-25, 1980

.2f r

Mr. James P. O'R lly, Director

[;

o Office of Inspect 1 and Enforcement U.S. Nuclear Regula Commission Regico II - Suite 310 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Reilly:

SEQUOYAH NUCLEAR PLANT UNIT 2 - ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT - NCR'S SQN EEB 8023 THROUGH EQN EEB 8039 (EXCLUDING SQN EEB 8034) - FICT n!TERLM REPORT The subject deficiency was initially reported to NRC-0IE Inspector R. W. Wright at October 24, 1980, in accordance with 10 CFR 50.55(e). We expect to submit our next report by January 23, 1981.

If you have any questier.s, plasse get in touch with D. L. Lambert at FTS 857-2581.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager i

Nuclear Regulation and Safety I

l Enclosure Mr. Victor Stallo, Director (Enclosure), y v

co:

Office of Inspection and Enforoement U.S. Nuclear Regulatory Commission Washington, DC 20555 30/7 S

/I 1

An E u.n c:::crture, Eme:ow 8012040 3

Y

(

.~

ENCLOSURE-

- SEQUOYAH NUCLEAR PLANT UNIT 2.

ENIRONMENTAL QUALIFICATION OF ELECTRICit. EQUIPMENT

-NCR'S SQNEEB8023 THROUGH SQNEEB8039

(EXCLUDING S(N EEB 8034) '

10 CFR 50.55(e)

FIRST INTERIM REPORT

-Description of Deficiency

. During the review of qualification records for electrical equipment

. quired by NUREG-0588,.a number of components were identified as-having inadequate documentation to verify their qualification levels for the harsh environments resulting from abnormal or accicent conditions at the plant. The affected equipment includes miscellaneous temperature switches, pressure switches,. flow meters, f

flow transmitters. radiation. monitoring ele =e.Ls, and solenoid valves in various plant systems. The subject components are. identified below:

NCR No.

Component No.

Model No.

Manufacturer SCNEEB8023 TS 74-43 T657A1540 Honeywell TS 74-44 TS 74-45 TS 74-46 i

SQNEEB8024 Essential Control Pall Trinity Air Dryer Corporation i

SQNEEB8025 PDT65-80 E13DL Foxboro

-82

-90

-97 SQNEEB8026 FM30-148 T23 ITT Conoflow SQNEEB8027 FM30-148A SW231-IT Transmation

-149

-149A TM67-84 SW611

-85

-92

-93

-100

-108

-109 SQNEEB8028 TSI-17A 17323-0 Fenwal

-17B

-18A.

-18B-SQNEEB8029-TS-30-103A.

T675A1540-Honeywell TS-30-104A

y-s

-NCR No.

. Component No.

Model No.

Manufacturer-SQNEEB8030 PDIS-30-148-3301 Dwyer PDIS-30-149 SQNEEB8031 FIS67-206 288A' ITT Barton

-209 FIS65-55A/B

-44E/F

-25A/B

-25C/D

-31A/B

-55C/D

-44A/B

-44C/D

-2SE/F

-31C/D

'FIS70-81 PDIS313-305 PDIS313-340 SQNEEB8032 FT 72-13 555 Bailey Controls 72-34 70-81A 70-81B 70-81D SQNEEB8033 RE90-130 N/A General Atc.:ic

-131

-106D-

-112D

-102

-103

-106

-106A

-106B

-106C

-112

-112A

-112B

-112C

-140

-141 SQNEEB8035 TS30-184 A19BAC Penn

-185

-190

-191

-192

-193

-207

-175

-176 7

w

NC' No.

Component No.

Model No.'

Manufacturer -

- SQNEB8035.

-177 A18BAC' Penn

-178

-179

-180

-182

-183

-194

-195

-196.

-197

-200

-186

-187

-201

-202 SQNEB8036 FS-30-184 3 11-6/1 F. W. Dwyer

-185

-190

-191

-192

-193

-146 3 11-7/1

-157

-194

-195

-196

-197

-200

-202

-207 SQNEB8037 PS-32-62 604GJR11-4905 Custom Component-

-88

-82

-35

-209 604GZ11-7029

-2.10 SQNEB8038 TS-30-103 18003-7 Fenwal TS-30-104 18003-7 SQNEB8039 FSV 1-181 HT3800B58RU ASCO

-182

-183

-184 FSV 313-223 HT8300C58RF

-225

-230

-323 SQNEEB8039

-FSV 77-127' WPXHV202-300-IF

NCR No.

_C_cpponent No.

Model No.

Manufacturer o

SQNEEB8039 F.W)90-108 HTX8320A22V ASCO

-109

-110

-114

-115

-116 FSV 30-298 HT8320A108

-299 FSV 30-3

-6

-60

-69

-146A HT8320A185^

-146B Interim Progress At present, documentation to prove this equipmer.t will operate satisfactorily in the harsh environment postulated during a high energy line break (HELB) or loss-of-coolant accident (LOCA) has not been located.

TVA is still gathering environmental quslification documentation on these components from their vendors. When data is not available, analyses are being performed by TVA to establish 'the ' qualification levels of the components.

h r

i 1

4

-