Forwards IE Bulletin 80-23, Failures of Solenoid Valves Mfg by Valcor Engineering Corp. Requires Estimate of Manpower Associated W/Corrective Actions
ML19345C180
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 11/14/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Rich Smith
VERMONT YANKEE NUCLEAR POWER CORP.
References
NUDOCS 8012040078
Download: ML19345C180 (1)


Text

.

s/

a.

f[

0, UNITED STATES

@ WL e

g NUCLEAR REGULATORY COMMISSION y

j REGION I t

631 PARK AVENUE

%,..../

x NG op PRuSstA, PENNSYLVANIA 19406 November 14, 1980 "

E Docket No. 50-271 N

Vermont Yankee Nuclear Power Corporation

~

ATTN:

Mr. Robert L. Smith E. ~.-.

Licensing Engineer

]

,]

25 Research Drive U

.:s Westborougn, Massachusetts 01581 0

M Gentlemen:

The enclosed IE Sulletin 80-23, " Failures of Solenoid Valves Manufactured by Valcor Engineering Corporation" is forwarded to you for action.

No written response is required.

In order to assist the NRC in evaluating the value/ impact of each Bulletin on licensees, it would be helpful if you would provide an estimate of the mancower expended in conduct of t!.a review and preparation of the recort(s) recuired oy the Sulletin.

Please estimata seoarately the mancower associated with corrective actions following identification of proolems througn the Sulletin.

If you desire additional information regarcing this mattar, please ontact this office.

Sincerely, C%

Scyca H. Grier Director

Enclosures:

1.

IE Bulletin No. 80-23 2.

List of Recently Issued IE Bulletins CONTACT:

0. L. Caphton (215-337-5256) cc w/encis:

Mr. Warren P. Murphy, Plant Superintendent Mr. W. F. Conway, Vice President and Manager of Operations i

l Mr. J. E. Griffin, President

[

Mr. L. 'H. Heider, Vice President l

l l

\\

Sonyao1%

J.

SSINS No.:

6820 Accession No.:

8008220257 IEB 80-23 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT D

~

PD WASHINGTON, D.C.

20555 i :s h

m;J j&

November 14, 1980 IE Bulletin No. 80-23:

FAILURES OF SOLEN 0IO VALVES MANUFACTURED BY VALCOR ENGINEERING CORPORATION

==

Introduction:==

Valcor Engineering Corporation (Valcor) has submitted 10 CFR Part 21 Reports addressing failures of Valcor solenoid valves used at nuclear power facilities.

These failures have occurred at nuclear facilities owned by Duke Power Company and Omaha Public Power District, and are purportedly limited to solenoid valves having part numbers (P/N's) V70909-21-1 and V70900-21-3.

The information presented in this bulletin is intended to shed light on the defective solenoid valves so tha.t appropriate actions can be taken to circum-vent the degradation of any safety-related system using such solenoid valves.

DISCUSSION:

The specific Valcor solenoid valves addressed herein were purportedly designed as Class IE components.

However, in light of the reported failures, it appears that neither the design nor the qualification tests were adequate for Class IE service.

Valcor has attributed the failures to a latent defect in the magnet wire.

Valcor believes that this defect manifests itself when the solenoid valves are continuously energized at elevated temperatures by an incompata-bility between the magnet wire's polyvinyl varnish coating and the wire's polyimide insulation which causes a dielectric breakdown leading to turn-to-turn shorts within the coil.

Valcor states that the above incompatability is Ifmited to solenoid valves having-P/N's V70900-21-1 and V70900-21-3, and that all customers affected by the aforementioned defect have been notified.

A listing of Valcor customers so notified and valves purchased follows.

CUSTOMER P.O. NO.

VALVE P/N QTY Anchor-Darling P-827 V70900-21-1,-3 24 Anchor-Darling N663 V70900-21-1 6

~Cesare Bonetti (Italy) 1535/79 V70900-21-3 10 Duke Power Company E95188-11 V70900-21-3 100 Ouke (Mill Power)

C-97733 V70900-21-1,-3 335 Duke Power Company E97822-11 V70900-21-3 70 Ralph Hiller HA-187-0:

V70900-21-3 14 Mill Power E52462-73 V70900-21-1,-3 20 Omaha Public Power Dist.

43472 V70900-21-3 19 Stone and Webster LOOO #43 V70900-21-3 8

l Copes Vulcan 911,553 V70900-21-1 4

TOTAL 610

)

IEB 80-23 November 14, 1980 Pages 2 of 3 Valcor's corrective actions include making arrangements for replacing existing coils with a newly designed coil using a 997 silicone varni.sh coating instead of the polyvinyl varnish.

Sample coils of the new design are scheduled to undergo qualification tests. We do not know the particulars of these tests, but Valcor has scheduled the first phase of these tests for completion by November 15, 1980, and has identified the second phase as an on going aging test.

Fort Calhoun has replaced twelve of its original sole.;oid valves with Valcor type V70900-21-3 valves, ten of which are located inside containment and two outside.

This substitution was made because the original solenoid valves did not meet the requirements of IE Bulletin No. 79-01.

However, subsequent to the replacement, Fort Calhoun has experienced five failures of these Valcor solenoid valves.

Each failure involved a solenoid vslve located inside contain-ment and designed for operation in the normally energized mode.

These two factors (i.e., continuously energized mode of operation and a somewhat elevated temperature inside containment) tend to support Valcor's contention regarding the failure mechanism.

ACTIONS TO BE TAKEN SY HOLDER OF OPERATING LICENSES:

1.

Determine whether Valcor solenoid valves having p/N's V70900-21-1 or -3 are used to perform any safety-related function at your facility.

If so, identify the safety-related systems using these solenoid valves, the total number of such solenoid valves used, and evaluate acceptability of continued operation with potentially defective solenoid valves.

A report of the results of the evaluation of continued operation shall be submitted within ten (10) days of the date of this bulletin and should include factors such as (a) operator's ability to promptly identify a failing or failed solenoid valve, (b) effect of solenoid valve failures on safety-related systems and subsequent operator actions required, and (c) possible degradation of the power suoply serving a failed solenoid valve and the effects on other components served by said power supply.

If no such solenoid valves are used, you need only submit a negative declaration to this effect within thirty (30) days of the date of this bullet-in and you need not respond to the remaining items.

2.

Licensees of operating plants using the aforementioned scienoid valves in safety-related applications shall periodically test the coils for potential turn-to-turn shorts in a manner that will not violate any LCO or cause any undesirable transient.

The tests should account for coil resistancechgngesduetotemperatureeffectsattributedtotheenviron-

~

ment and to I R losses in the coil to provide accurate indications of changes in resistance due to turn-to-turn shorts.

These tests are to be initiated within ten (10) days of the date of this bulletin.

The following schedule is recommended until the units are replaced with qualified units:

(a) Daily for solenoid valves operated in a normally energized mode; (b) Weekly for solenoid valves operated in a normally deenergized mode.

i

I7 IE8 80-23 November 14, 1980 Pages 3 of 3-Whenever-the tests indicate that ten percent or more of the coil turns have been shorted, said solenoid valve, or its coil, shall be replaced with a new unit.

3.

Licensees of operating plants shall submit a report within forty-five

'(45) days of the date of this bulletin describing their longer term corrective action plan and the date by which the corrective actions will be imolemented.

As a minimum, the longer term corrective measures should include the replacement of the coils with fully qualified coils.

New solenoid valve assemblies (i.e., a repaired unit with a replacement coil or a completely new unit) shall be demonstrated to be qualified for its safety-related application per the applicable requirements of IEEE 323-1974, IEEE 3a4-1975, IEEE 382-1972 and IE Sulletin No.79-01B and supplements thereto.

ACTIONS TO BE TAKEN SY HOLDERS OF CONSTRUCTION PERMITS:

1.

Determine whether Valcor solenoid valves having P/N's V70900-21-1 or -3 are to be used to perform safety-related functions at your facility.

If so, a report addressing this matter shall be sucmitted by the earlier of the two following dates:

(a) within ninety (90) days of the date of this bulletic; (b) two weeks prior to the date by which you expect to receive an operating License.

The above report should indicate your plans to replace said valves prior to commencing operation, if this is the case.

Otherwise, if you propose to commence operation prior to replacing said valves, the report should indicate the safety related systems where such valves are to be used, and should include an evaluation of the acceptability of operating with potentially defective valves.

This evaluation should address factors such as your proposed test plan, operator's ability to promptly identify a failing or failed valve, effect of solenoid valve failure on safety-related systems and subsequent operator actions required, and the preventive measures you plan to implement to circumvent the effects of failures of these valves.

If no such valves are to be used in your faciiity, submit a negative-declaration to this effect within forty-five (45) days of the date of this bulletin but prior to the date by which you expect to receive an operating ifcense.

The above requested reports thall be submitted to the director of the appropriate NRC region within time stipulated for each item in the this bulletin.

A copy of each report shall'be forwarded to the Director, Division of Resident and Regional Reactor Inspection, Office of Inspection and Enforcement, United States Nuclear Regulatory Commission, Washington, D. C. 20555.

Approved by GAO, B180225(R0072);- clearance txpires November 30, 1980.

Approval was given under a blanket clearance specifica 11y for identified generic problems.

\\

J l

l i

IE Bulletin No. 80-23 November 14, 1980 RECENTLY ISSUED IE BULLETINS Bulletin Subject Date Issued Issued To No.

80-22 Automation Industries, 9/12/80 All holders of a Model 200-520-008 Sealed-radiography license Source Connectors 80-21 Valve Yokes Supplied by 11/6/80 All holders of a Malcolm Foundry Company, Inc.

power reactor OL or CP Revision 1 Baron Loss from 8/29/80 All holders to 79-26 BWR Control Blades of a SWR p<wer reactor OL Revision 1 Failures of Mercury-8/15/80 All holders of a to 80-19 Wotted Matrix Relays in power reactor Reactor Protective OL or CP Systems of Operating Nuclear Power Plants Designed by Combustion Engh eering i

80-20 Failires of Westinghouse 7/31/80 All holders of a Type W-2 Spring Peturn to power reactor OL Neutral Control Switches or CP 80-19 Failures of Mercury-7/31/80 All holders of a Wetted Matrix Relays in power reactur OL Reactor Protective Systems or CP of Operating Nuclear Power Plants Designed by Combustion Engineering 80-18 Maintenance of Adequate 7/24/80 All holders of a Minimum Flow Thru PWR power reactor Centrifugal Charging Pumps OL or CP Following Secondary Side High Energy Line Rupture Supplement 3 Failure of Control Rods 8/22/80 All holders of a-to 80-17 to Insert During a BWR power reactor Scram at a BWR OL or CP Supplement 2 Failure of Control Rods 7/22/80 All holders of a to 80-17 to Insert During a Scram BWR power reactor OL at a BWR Supplement 1 Failure of Control Rods 7/18/80 All holders of a BWR to 80-17 to Insert During a Scram power reactor at a BWR OL or CP

..