ML19345B687

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in IE Insp Repts 50-259/80-34,50-260/80-27 & 50-296/80-28.Corrective Actions:Administrative Instructions Modified to Ensure Fire Watch Assigned to Vital Area Issued Key Card for Access
ML19345B687
Person / Time
Site: Browns Ferry  
Issue date: 11/05/1980
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19345B682 List:
References
NUDOCS 8012020345
Download: ML19345B687 (2)


Text

'

  • (")

i TENNESSE'; VALLEY AUTHORITY CHATTAP.OOGA, TENNESSEE 374ol 400 Chestnut Street Tower II l^

qf Nov' nt'er 5, 1980 e

Mr. James P. O'Reilly, Director Office of Inspection and Enforcement U.S. Nucleer Regulatory Commission Region II Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Reilly:

Enciosed is our response to R. C. Lewis' October 9,1080, letter, RII:RFS 50-259/80-34, -260/80-27, and -296/80-28, concerning activities at Browns Ferry Nuclear Plant which appeared to be in noncompliance with NRC requirements.

Very truly yours, TENNESSEE VALLEY AUTHORITY Mills, Manager 4.

Nuclear Regulation and Safety Enclosure 80120 2 03 W

,, co., o,,,,,,,,,, e m,,,,,,

3 f

ENCLOSURE OFFICE OF INSPECTION LETTER RII:RFS 50-256/80-34, -260/80-27, -296/80-28, DATED OCTOBER 9,1980, R. C. LEWIS TO H. G. PARRIS NOTICE OF VIOLATION Based on the NRC inspection of August 1-31, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below.

.tese items have been categorized as described in correspondence to you dated December 31, 1974.

Technical Specification 3 11.E.4 requires in part that a continuous fire watch shall be established immediately if the carbon dioxide (CO ) fire protection systen is lost 2

to a cable spreading room.

Contrary to the above, on August 5,1980 from approximately 11:00 r.m. to 11:45 a.m., a continuous fire watch was not

~

vided for the cable spreading roons for Units 1, 2, and 3 anile tie CO system was inoperable for repairs.

2

RESPONSE

Corrective Steps Taken and Results Achieved Continuous surveillance of the room was initiated inmediately by the shift engineer when the event was brought to his attention.

Corrective Steps Which Vill Be Taken To Avoid Further Noncomoliance Administrative instructions will be modified to ensure that a fire watch assigned to a vital area will be issued a key ca.'d for access to the area.

Date Phen Full Compliance Will Be Achieved Full compliance was achieved on August 5, 1980, in that the required continuous fire watch was posted. Administrative instruction changes to prevent recurrence were completed on November 3, 1980.

  • mm L

mmm~