Forwards LERs 80-063/03L-0 & 80-067/03L-0
Date released: 12/25/2019 Download: ML19345A845


LER 80-067/03L-0:on 801020,svc Water a Train Battery Sys Was Declared Inoperable.Caused by Close Terminal Post Proximity & Poor Terminal Post Seal Design.Battery Was Cleaned & Placed on Charge
ML19345A865
Person / Time
Site: Farley 
Issue date: 11/20/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345A865 (2)
LER 80-063/03L-0:on 801020,while Performing Emergency Core Cooling Valves Inservice Test,Valve 1-CVC-MOV-115D Would Not Open from Main Control Board.Caused by Contact Arm 4 Being Out of Adjustment.Contact Arm Was Readjusted
ML19345A860
Person / Time
Site: Farley 
Issue date: 11/20/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345A860 (1)
Forwards LERs 80-063/03L-0 & 80-067/03L-0
ML19345A844
Person / Time
Site: Farley 
Issue date: 11/20/1980
From: Clayton F
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345A844 (1)