Inquiry Rept 50-29/73-01Q:surface Defects Found on Eight Isolation Valves During Ndt.Defects Removed by Surface Grinding.Weld Overlay Application,To Meet Min Wall Thickness Requirements,Completed
ML19345A269
Person / Time
Site: Yankee Rowe
Issue date: 03/14/1973
From: Loibl E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML19345A268 List:
References
50-029-73-01Q, 50-29-73-1Q, NUDOCS 8011180416
Download: ML19345A269 (1)


Text

.

y

,,2,,,.a

,e--

- ~ ~ --- -

.1 --

2 UNITED STATES

/p, g,%,,%

g;

.l ATOMIC ENERGY COMMISSION

.]

DIRECTOR ATE OF REGut.ATORY OPERATIONS g

9

}f.

't.;

i L

f-970 BRO AD STREET NEWARK, NEW JERSEY 07102 Inn e r

f T

j RO INQUIRY REPORT NO. 50--29 /73-01Q t

[:j

Subject:

Yankee Atomic Electric Co.

7 i

20 Turnpike' Road f

Westboro, Massachusetts-

[f License No.:

DPR-3

?

Facility:

Yankee Rowe 3

.l Rowe, Massachusetts

Title:

Equipment Deficiency - Isolation l'

Valve Surface Defects Prepare #. by:

M/Irrb//fiJ j

E. R. Loibl, Actirig Sr. Reactor Inspector Date' A.

Date and Manner AEC was Informed:

In response to Region I questions concerning the valve wall thickness verification program (

Reference:

Region I letter to Yankee Atomic Electric Company dated February 7,1973 and Yankee Atomic Electric Company response dated March 7, 1973), the licensee informed Region j

I by telephone on March 13, 1973 that surface defects were discovered on the reactor coolant isolation valves.

B.

Description of Particular Event or Circumstance:

j The licensee stated that during preliminary surface cleanup prepara-i tions, being done prior to adding veld overlay to the reactor coolant I

I isolation valves, nondestructive testing (liquid penetrant) re-vealed surface defects on all eight of the valves. Most of the

~

crack like-defects described by the licensee as being discontinuities, I

.were stated to be quite shallow (approximately.030") and the maximum defect was approximately.120" deep and 1/2" long. All

.j-of the defects were stated to have been removed by surface grinding.

)

Removal of the defects was stated to have been verified by non-

~

l destructive testing (liquid penetrant).

The work of applying weld overlay (to meet minimum wall thickness requirements) was stated by the licensee to have been completed.

C.

Action by Licensee:

I f

}

A written report to the AEC 'will be submitted by the licensee 1

addressing the defects found and corrective actions taken.

\\