ML19344F573

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-30, Potential for Unacceptable Interaction Between Control Rod Drive Scram Function & Nonessential Control Air at Certain GE BWR Facilities. No Specific Action or Response Requested
ML19344F573
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
Issue date: 08/20/1980
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Linder F
DAIRYLAND POWER COOPERATIVE
References
NUDOCS 8009150455
Download: ML19344F573 (1)


Text

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

/

'o UNITED STATES NUCLEAR REGULATORY COMMISSION y

3 n

U A

YkI[o*E REGION lli 799 ROOSEVELT ROAD

%g..%./,8 GLEN ELLYN,lLLINOIS 60137 Docket No. 50-409 Dairyland Power Cooperative ATIN:

Mr. F. W. Linder General Manager 2615 East Avenue - South La Crosse, WI 54601 Gentlemen:

This Information Notice No. 80-30 is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request licensee actions.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Sincerely, QA S.Yc " 9 "

hiamesG.Keppler Director

Enclosure:

IE Information Notice No. 80-30 cc w/ encl:

Mr. R. E. Shimshak, Plant Superintendent Central Files Director, NRR/DPM Director, NRR/ DOR AEOD Resident Inspector, RIII PDR Local PDR NSIC TIC Mr. John Duffy, Chief Boiler Inspector, Department of Industry, Labor and Human Relations 80091 50 I a.-

SSINS No.:6870 Accession No.:

8006190057 IN 80-30 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 August 19, 1980 IE Information Notice No. 80-30:

POTENTIAL FOR UNACCEPTABLE INTERACTION BETWEEN THE CONTROL ROD DRIVE SCRAM FUNCTION AND NON-ESSENTIAL CG,JTROL AIR AT CERTAIN GE BWR FACILITIES Continued NRC evaluation of possible failure modes of the control rod drive system related to the Browns Ferry event (IE Bulletin 80-17), has identified a potentially significant single failure mechanism whlch could degrade the scram function.

The slow loss of non-essential control air pressure could degrade the scram function at certain facilities which have relatively poor communica-tion between the scram discharge volume (SDV) and the scram discharge instru-mented volume (SDIV) such that the SDIV drains more rapidly than the SDV drain rate into the SDIV.

The significance of such a single failure warrants transmission of an interim assessment by the NRC Office for Analysis and Evaluation of Operational Data as an early notification of a possibly significant matter that is still under review by the NRC staff.

It is expected that recipients will review the

' ~

information for possible applicability to their facility.

No specific action or response is requested at this time.